Baxi Solo 3 30 PF System Installation And Servicing Instructions page 12

Wall mounted powered flue system boiler gas fired central heating unit
Table of Contents

Advertisement

5.0
Site Requirements - Page 12
5.3
Flue Position (Cont)
WARNING - The addition of anything that may interfere
with the normal operation of the appliance (e.g. FLUE
DAMPERS, ECONOMISERS,etc.) without the express
written permission of Baxi Heating Ltd could invalidate
the appliance warranty and Infringe the GAS SAFETY
(Installation and Use) REGULATIONS.
If a terminal is less than 2 metres (78¾ in) above a
balcony, above ground or above a flat roof to which
people have access then a suitable terminal guard must
be provided.
6. Table 2 and Fig. 10 show the positioning of the flue
terminal relative to buildings and other structures.
7. The dimensions of the flue terminal are shown on page 6.
5.4 Flue Dimensions
1. Flue extensions are available as optional extras for
installations up to 3 metres (118
2. Vertical flue kits are available up to 4 metres in
length. Vertical twin flue kits are available up to 15
metres In length.
3. The standard flue supplied with the appliance is suitable
for use with flue lengths between 100mm (4in) and 500mm
5
(19
/
in).
8
NOTE: Maximum flue length when flued to the left or
right is
350mm - Left Hand Flue
330mm - Right Hand Flue
4. Where it is intended to pass the flue through a
combustible wall or timber framed dwelling, reference should
be made to the Institute of Gas Engineers document UP7 -
Guide for Gas Installations in Timber Framed Dwellings.
5. If the flue is more than 1 metre (39
required that it is supported.
6. All above dimensions are taken from the respective
faces of the outer case.
1
/
in) horizontal.
8
3
/
in) long, it is
8