Checking The Minimum Gas Pressure Switch Setting - REMEHA Gas 460 S Technical Instructions

Gas-fired boilers
Hide thumbs Also See for Gas 460 S:
Table of Contents

Advertisement

In the factory, the progressivity is set to minimum (low start-up
pressure).
Depending on the installation conditions, adjust the progressivity
setting in order to guarantee optimum boiler start-up.

5 Checking the minimum gas pressure switch setting

The minimum gas pressure switch on the safety valve is set in the
factory to a value of 12.5 mbar, which corresponds to the setting for
natural gas.
To operate on propane, set the start-up pressure to 20 mbar.
06/02/06 - 300005247-001-B
Setting the start-up progressivity (or initial flow)
- Unscrew the protection cap G. Use like a spanner to turn the
setting rod H until you obtain the desired initial flow.
- Put the cap back in place.
Remeha Gas 460 S
15