Normal operating cycle
Operating cycle on safety (start up without flame signal)
Required input signals
Box output signals
Thermostatic request at 2nd stage
Operation 2nd stage
A
Start of operation
B
Formation of flame in ignition burner
BR1
1st stage
BR2
2nd stage
SF
Burner flame signal
TA
Ignition transformer
TCH1 Boiler thermostat 1 Speed
TCH2 Boiler thermostat 2 Speed
VA
Safety lockout warning light
VG
Ignition burner valve + Safety valve VS
ts
Safety time: maximum 10 seconds
tstab
Flame stabilisation time: 5 seconds
tvz
Pre-ignition time: 10 seconds
tw
Waiting time: 0 seconds