Commissioning; Power-Up Options Menu - Securacom SEC8 Installation Manual

8 zone intruder alarm system
Hide thumbs Also See for SEC8:
Table of Contents

Advertisement

Commissioning

Once ALL connections have been made to the control panel and
power is ready to be applied, you should read this section before
continuing.
The control panel leaves the factory programmed with default
settings and when the system is powered up for the first time the
default settings are in use. If the factory defaults need to be
reloaded in the future, please see "Power-up Options Menu".
Connect the black battery lead to the negative (–) terminal of
the standby battery and the red battery lead to the positive
(+) terminal of the standby battery. The green power LED on
the main PCB will light.
If the system enters into an alarm condition, enter the
default master user code
then stop.
To access the Engineer Programming Menu, enter the
default engineer code
show:
En
Engineers Menu
Location:----
LED
Program the system as described in the next section
(Programming the Control Panel).
Carry out a walk test as described on page 37. Remember
that some powered detectors (e.g. PIRs and combined
technology detectors) take several minutes to warm up
before they become operational.
Test the internal sounder, external sounder and strobe as
described on page 37.
P0031-LI-01.00
. The alarm tone will
5678
. The remote keypads will
1234
LCD
Replace the lid and secure with the lid screw supplied - do
not over-tighten.
Enter
to leave the programming menus.
*99
The Service light will be flashing to indicate that action is
required. Switch on the mains supply to the control panel.
The Service light will stop flashing and stay on continuously.
Installation is now complete and the system is ready for use.
Please ensure the system users are provided with adequate
training on operating the alarm system.

Power-Up Options Menu

When power is applied to the system, the control panel enables
the "Power-Up Options Menu" for 10 seconds. During this period
the control panel status LED flashes between red and green and
the system will accept the following commands:
Command
Description
Default Engineer Code
Entering this command will set engineer access code
*0#
back to 1234.
Save as Factory Defaults
Entering this command will save the current control
*3#
panel program configuration as the NEW factory
default profile.
Set UDL Password
Entering this command will set the UDL password to
*6#
123456.
Load Factory Defaults
Entering this command will set all control panel
*9#
program configuration options to the factory default
settings.
13