Single Eol - N/C; Double Eol; Triple Eol; Loudspeaker Connections - Securacom SEC8 Installation Manual

8 zone intruder alarm system
Hide thumbs Also See for SEC8:
Table of Contents

Advertisement

Single EOL - N/C

This wiring configuration should be used when connecting
detection devices that only have a normally closed alarm output.
Connect the detector as shown below and ensure that the zone is
programmed for "Single EOL – N/C" operation, see page 19.
Alarm
3K3
1 Detector

Double EOL

This wiring configuration should be used when connecting
detection devices that have a normally closed alarm and tamper
output. Connect the detector as shown below and ensure that the
zone is programmed for "Double EOL" operation, see page 19.
Alarm
Tamper
2K2
E.O.L
1 Detector
P0031-LI-01.00
Zx Com
Zy
Alarm
Alarm
3K3
2 Detectors
Zx Com
Zy
Alarm
Tamper
Alarm
Tamper
2K2
E.O.L
2 Detectors

Triple EOL

This wiring configuration should be used when connecting
detection devices that support triple EOL configuration, this will
allow the system to monitor alarm, tamper fault and mask.
Connect the detector as shown below and ensure that the zone is
programmed for "Triple EOL" operation, see page 19.
1 Detector

Loudspeaker Connections

By default panel output 4 operates as a loudspeaker driver. It is
capable of driving one 16Ω or two 8Ω wired in series as shown
below:
The volume level can be programmed, please refer to page 23 for
details. The loudspeaker can also be tested, please refer to page
23 for further details.
Panel output 4 must be programmed as "Not Used" in order for it
to function as a loudspeaker driver.
Zx Com
Zy
Fault
Alarm
Tamper
2K2
E.O.L
Ω
16 Loudspeaker
Ω
8 Loudspeaker
Ω
8 Loudspeaker
11