Note!
Mains supply requirements
High power equipment may, due to the primary current drawn from the mains supply, influence the
power quality of the grid. Therefore connection restrictions or requirements regarding the
maximum permissible mains impedance or the required minimum supply capacity at the interface
point to the public grid may apply for some types of equipment (see technical data). In this case it
is the responsibility of the installer or user of the equipment to ensure, by consultation with the
distrubution network operator if necessary, that the equipment may be connected.
Make sure that the welding power source is connected to the correct supply voltage
and that it is protected by the correct fuse rating. A protective earth connection must
be made in accordance with regulations.
Rating plate with supply connection data
NOTE! The welding power source is designed for connection to a 400 volt
system with four conductors.
Recommended fuse sizes and minimum cable area
Tig 3001i
Mains voltage
Mains cable area mm
Phase current I
eff
Fuse
anti--surge
type C MCB
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with Swedish
regulations. Use the welding power source in accordance with the relevant national regulations.
bt37e
400 V 3μ 50 Hz
2
4G4mm
10 A
16 A
16 A
2
- - 19 - -