Minimum Clearances, Parallel Installation, Corner Installation; Wall And Ceiling Clearances; Mantel Clearances; Hearth Requirements - Vermont Castings Intrepid INDVRCB Homeowner's Installation And Operating Manual

Vermont castings intrepid series direct vent, rear vent gas heater
Hide thumbs Also See for Intrepid INDVRCB:
Table of Contents

Advertisement

Parallel Installation: Minimum Clearance
and Flue Centerline
"
(476 mm)
4"
(102 mm)
Fig. 3 Parallel Installation, minimum back and side clearance.
Corner Installation: Minimum Clearance and
Flue Centerline
7 "
(190 mm)
Max. Vent
Length
24" (610 mm)
2"
(51 mm)
Fig. 4 Corner installation, minimum corner clearance and flue
centerline.

Wall and Ceiling Clearances

4"
(102 mm)
Sidewall/
Trim
Fig. 5 Alcove and ceiling clearances.
20012761
Max. Vent
Length
C L
24" (610 mm)
2 "
(64 mm)
4"
(102 mm)
2" (51 mm)
9"
(230 mm)
Max. Mantel
Width
Refer to
Fig. 6
(63 mm)
Rear Wall
Intrepid® Direct Vent - Rear Vent Gas Heater
Combustible
Mantel or Trim
Materials
B
3" (75mm) Min.
A (Max.)
ST947
(230 mm)
(190 mm)
(152 mm)
(114 mm)
A = Depth of Mantel and/or Top Trim
B = Height from Top of Heater
Fig. 6 Mantel / top trim clearances.
The Intrepid Heater must be installed on rigid flooring. When
the heater is installed directly on any combustible surface
other than wood flooring, a metal or wood panel extending
ST948
the full width and depth of the unit must be used as the
hearth. There are no other hearth requirements.
2 "
ST949

Mantel Clearances

A
9"
(270 mm)
7¹⁄₂"
(230 mm)
ST382
6"
Pinnacle
(190 mm)
4¹⁄₂"
mantel clearances
(152 mm)
6/13/00 djt
3"
(76 mm)
(114 mm)
1¹⁄₂"
(38 mm)

Hearth Requirements

Noncombustible
Materials
ST382
B (Min.)
10¹⁄₂"
9"
7¹⁄₂"
6"
4¹⁄₂"
3"
(76 mm)
7