step 5.
Make sure that the connections are screwed tight; (use a 10 mm or M6
spanner or wrench).
3.5
C
ONNECTING THE
The terminal block is located on the PCB (see Illustration 1). The 230 V
external equipment must be connected to the inverter by means of a
three-wire cable. Use a cable with a flexible core and a cross section of 2.5
mm².
Connection procedure 230 V
step 1.
Unscrew the four screws of the front panel .
step 2.
The 230 V
equipment may be directly connected to the
AC
connector block on the left side of the PCB, with a
three-wire cable. The connections are clearly coded and
from left to right they are: 'L', 'N', and 'PE'. The AC
output is automatically current limited in the event of a short
circuit on the output (see section 2.1).
The inverter will be seriously damaged if an external
voltage is connected to the inverter's AC-block. This
damage will occur regardless of the switch position of the
step 3.
Replace the front panel with the four screws.
18
230 V
cables
AC
inverter is 'ON' or 'OFF'.
CABLES
AC
manual
AC