IPPLE VOLTAGE PROTECTION
The Victron Energy Phoenix 12/300, 12/500, 24/500 and 24/900 are
protected against too high ripple voltage at the input. If the rms value of
the input voltage-ripple exceeds 10% of the nominal DC input voltage,
the inverter will state an alarm; the LED 'low batt.' and the LED
'overload' will flash. If the previous alarm situation is on for a period of
over 21 minutes, the inverter will switch off and the following alarm
indication can be seen; the LED 'low batt.' and the LED 'overload'
illuminate.
The inverter has to be resetted before it will continue operation.
Resetting can be done by means of switching the inverter off and on
again.