Operation Check & Aeration Settings Adjustment
Operation Check
Turn the fi replace fl ame up and down using the
remote control to confi rm that the full range of inputs
is achieved—see the remote control operation
instructions on pages 30-35.
Aeration Settings
Light the fi re and allow the unit to warm up for 10–15
minutes to evaluate the fl ame picture. Burners are
equipped with an adjustable shutter to control primary
aeration. See the fi gures below. The shutters are
factory-set to an aeration gap which will give optimum
performance for the vast majority of installations.
Air Shutters
NG Air Shutter
Slider & Cover
The side shrouds are required to install the front on the
appliance. They are supplied with the engine.
Fit them to the appliance outer case as indicated
(2 screws/side).
NG
Close
Open
Close
Open

Side Shrouds Installation

In a few unusual installations, the fl ame picture may
be improved by adjusting the aeration. The need for
adjustment should be determined only by operating the
appliance with the ceramic logs and window installed.
Increasing aeration (open) will cause the fl ames
to appear more transparent and blue showing more
ceramic log glow.
Decreasing aeration (close) will cause the fl ames to
appear more yellow or orange showing less ceramic
log glow.
Too little aeration may result in black carbon
forming and dropping into the fi rebox.
Flashback
shield (for
LPG only)
LPG Air Shutter
Slider
Door hinge
points should
face inwards
INSTALLATION
LPG
Close
Open
25