Oil Or Gas Connection; Specific Technical Information Supplied With The Burner - DeDietrich GT 430 A Operating Instructions Manual

Hide thumbs Also See for GT 430 A:
Table of Contents

Advertisement

1 Specific technical information supplied with the burner

The boiler and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psi (3.5kPa),
The boiler must be isolated from the gas supply piping system
by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa),
The boiler shall be installed such that the gas ignition system
components are protected from water (dripping, spraying, rain,
etc.) during appliance operation and service (circulator
replacement, condensate trap, control replacement, etc.),
The boiler and its gas connection must be leak tested before
placing the boiler in operation,
After placing the boiler in operation, the ignition system safety
shutoff device must be tested,
Provision for vent, bleed and gas relief lines (when applicable),
A sediment trap must be provided upstream of the gas controls,
Location of manual main shutoff valve outside the jacket when
codes require.
36
82294154

Oil or gas connection

Follow the information and documentation as supplied with
the burner, regarding:
The specific installation requirements, wiring, fuel supply and
piping and all adjustments of the air and fuel and start-up
procedure as be followed as supplied with the burner
documentation
Consult the burner manufacturer regarding the required
maintenance of the burner and the service intervals.
The entire heating system must be check once each heating
season.
Do not start the burner/boiler unless all access cover and
panels are in place.
11-20-09

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt 330 a

Table of Contents