9.2 Operation and Set-up
The Matrix employs a pneumatic modulation system. This modulation system increases or decreases the velocity of the combustion
blower, to meet the demand for heating. The gas valve senses this change in blower pressure and introduces the required amount of
gas to ensure correct combustion. The Sentry reads the boiler water temperature, compares it to the set point, and adjusts the burner
firing rate accordingly by varying the speed of the combustion blower.
The (Blue) Fan Controller communicates the appropriate demand and temperature set point to the (Red) Boiler Controller via a
series of digital and analog inputs. Table 9.3 shows the Boiler Controller's response to the demand. For more information on
'RESET MODE' see section '9.3 Outdoor Sensor Operation'.
Table 9.3 Conventional vs. Outdoor Reset Mode
Standby/Storage
Storage
Condition
Set Point
Burner On
Burner Off
Heat Circ.
Standby/Storage
Storage
Condition
Set Point
Burner On
Burner Off
Heat Circ.
Note 1. SP (Setpoint) received from Matrix Fan Controller.
9.2.1 Setting Matrix Boiler Control (Sentry)
Programming is accomplished by a series of three push buttons located on the bottom side of the control. (Function,
enter the programming mode, press the function key once. To scroll through the various menu options depress
displayed. To alter the value press Function once, and the current value will be displayed, then use
the desired value is obtained. To enter the selected value press Function, which will return to the menu. When all desired values are
selected, scroll to the RUN menu, and press Function, which exits the Programming Mode and initiates normal operation. A safety
feature has been added to ensure that if the control is left in the Program Mode, the unit will turn off if left in program mode longer
than 30 seconds without receiving an input. Press Function once to continue programming or to start boiler operation.
Primary
Forced Air
Mode
Call (W1)
Storage
Heat (W1)
Off
On
Note 1
-
160°F
SP
Note 1
-
140°F
SP
-
180°F
210°F
Off
On
On
Primary
Forced Air
Mode
Call (W1)
Storage
Heat (W1)
Off
On
Note 1
-
160°F
SP
Note 1
-
140°F
SP
-
180°F
210°F
Off
On
On
Auxiliary
Shared Call
Forced Air
Forced
Call (W2)
Air/Hydronic
Aux Heat
Shared (W1/W2
(W2)
and H)
Greater of SP/ HI
Note 1
HI
and HYD
Greater of SP/HI
Note 1
HI
and HYD
210°F
210°F
On
Auxiliary
Shared Call
Forced Air
Forced
Call (W2)
Air/Hydronic
Aux Heat
Shared (W1/W2
(W2)
and H)
Greater of SP/ HI
Note 1
HI
Calc.
and HYD
Calc.
Greater of SP/ HI
Note 1
HI
Calc.
and HYD
Calc.
210°F
210°F
On
34
Hydronic
Demand (H)
Hydronic Call
HYD
HYD-DIF
HYD + 10
On
On
Hydronic
Demand (H)
Hydronic Call
HYD
Calc.
Calc.
HYD
-DIF
Calc.
Calc.
HYD
+ 10
Calc.
On
On
↑
until the menu is
↑
↓
for up, and
DHW
Demand
Domestic
Only
H2O to
H2O+30
H2O+30
210°F
On
DHW
Demand
Domestic
Only
H2O to
H2O+30
H2O+30
210°F
On
↑
↓
and
). To
for down, until