ADDITIONAL FEATURES

LIMIT SETUP WITH A REMOTE CONTROL

ADJUST THE LIMITS
If the limits have already been set the operator will exit the limit setting mode after
resetting each limit.
Set the Close Limit Only
1
Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter
limit setting mode.
2
Press and hold the CLOSE button on the remote control until the gate reaches
the desired close position. The gate can be jogged back and forth using the
OPEN and CLOSE buttons on the remote control.
3
Once the gate is in the desired close position, press and release the STOP button
on the remote control.
4
Press and release the CLOSE button on the remote control again to set the close
limit.
When the close limit is set properly the operator will automatically exit limit setting
mode.
Set the Open Limit Only
1
Press and release the SET OPEN and SET CLOSE buttons simultaneously to enter
limit setting mode.
2
Press and hold the OPEN button on the remote control until the gate reaches the
desired open position. The gate can be jogged back and forth using the OPEN
and CLOSE buttons on the remote control.
3
Once the gate is in the desired open position, press and release the STOP button
on the remote control.
4
Press and release the OPEN button on the remote control again to set the open
limit.
When the open limit is set properly the operator will automatically exit limit setting
mode.
LIMIT SETUP WITH A REMOTE CONTROL
3-Button Remote Control programmed for OPEN, CLOSE, and STOP