Storing The Ups And Batteries; Testing Batteries - Minuteman 6-10KVA Tower User Manual

Online ups
Table of Contents

Advertisement

4. Disconnect the internal battery connectors
5. Replace the UPS front cover

6.3 Storing the UPS and Batteries

If you store the UPS for a long period, recharge the battery every 6
months by connecting the UPS to utility power. The batteries charge to
90% capacity in approximately 4 hours. However, it is recommended
that the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has passed and the batteries were never recharged, do not use the UPS.
Contact your service representative.
When to Replace Batteries
When the status summary screen displays the UPS fault icon with the
"Service Battery" alarm and the audible alarm sounds continuously, the
batteries may need replacing. Contact your service representative to
order new batteries.

6.4 Testing Batteries

For a battery test, please check:
The batteries must be fully charged.
The UPS must be in Normal mode with no active alarms.
The load must be higher than 10%.
To test batteries:
1
Connect the UPS to utility power for at least 48 hours to charge
the batteries.
2
Press the
selection and scroll down to the Control menu using the
button.
3
Press the
4
Use the
5
Press the
button for one second to go to the main menu
button to enter the Control menu.
button to scroll to the Battery Test option.
button to start the battery test.