Table Of Contents Introduction Controls and Indicators Installation Operation Troubleshooting Replacing the Battery Obtaining Service Specifications Limited Product Warranty A1. Declaration of Conformity...
Standard for the Protection of Electronic Computer/Data Processing Equip- and manufactured to provide many years of trouble free service. Please read ment ANSI/NFPA 75. this manual before installing your Entrepid Series UPS, models ETR550LCD, ETR700LCD, ETR1000LCD, ETR1500LCD as it provides important informa- CAUTION!
Page 4
NOTICE! The output of this device is not sinusoidal. It has a total harmonic distortion and maximum single harmonic as below: After removing your UPS from its carton, it should be inspected for damage that ETR550LCD Total harmonic 42.6% Single harmonic 20.3% may have occurred in shipping.
Chapter 2: Controls and Indicators Load Capacity Bar Graph: Displays the amount of load connected to the UPS in the AC and Battery mode as 20%, 40%; 60%, 80%, 100%. CONTROL PANEL When the amount of load attached to the UPS exceeds 110% of its power rating;...
Input Power Plug Output Power Receptacles Use CAUTION, the UPS is heavy. Remove the UPS from the shipping box ETR550LCD 4-NEMA 5-15R Battery Backup & Surge and set on a desk or a bench top. NEMA 5-15P W/6 ft cord...
Page 7
POWER MONITORING SOFTWARE this manual). DO NOT PLUG EXTENSION CORDS, ADAPTER PLUGS, SURGE This UPS supports Minuteman's SentryHD power monitoring software. Please STRIPS OR POWER STRIPS INTO THE OUTPUT RECEPTACLES OF THE go to our web site at www.minutemanups.com/support, then look under Down- UPS.
Chapter 4: Operation TEST BUTTON To perform a ten-second user invoked battery test: With the UPS in the AC normal SYSTEM OVERVIEW mode, press and hold the On/Off/Test Button until the alarm sounds four beeps, and This Line-Interactive UPS protects computers, servers, telecom systems, VoIP sys- then release.
Chapter 5: Troubleshooting ALARMS ON BATTERY Cause / What To Do When the UPS is operating on the batteries, the AC normal icon will extinguish, Symptom / Error Code the On-Battery icon will illuminate, the LCD will display the estimated runtime Press the On/Off/Test button and release after one UPS will not turn on.
UPSs contain sealed non-spillable maintenance-free lead acid batteries. CAUTION: DO NOT pull the battery module out by pulling on the battery wires. ETR700LCD ETR1000LCD ETR550LCD ETR1500LCD Model # 9. Slide the new battery module into the UPS. Battery Module BM0064...
13. The UPS is now ready for the normal operation. Para Systems Inc. NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the battery MINUTEMAN UPS 1809 W. Frankford Road, Suite 150 module, a user invoked battery test must be performed to clear the Weak/Bad Carrollton, TX 75007 Battery Alarm.
8-hours to 90% capacity from a full load discharge Typical Battery Life 3 to 5 years. Environmental factors do affect battery life. High Model Number ETR1500LCD ETR550LCD ETR700LCD ETR1000LCD temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life.
Systems only covers faulty parts. Para Systems products that are depot repaired or replaced pursuant to this warranty shall only be warranted for the unexpired portion of Manufacturer’s Name: Para Systems, Inc. (MINUTEMAN UPS) the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.