Minuteman 6-10KVA Tower User Manual page 52

Online ups
Table of Contents

Advertisement

Voltage
Power
Regulation
Factor
0.9 lag
±1%
Table7. Environment and safety
Temperature
0°C-40°C
Note: if the UPS is installed or used in a place where the altitude is
above than 1000m, the output power must be derated in use, please
refer to the following:
Altitude (M)
1000
Derating
100% 95%
Power
Frequency
Distortion
tolerance
Synchronized
THD<2%
50/60Hz±10%
Full load
in Line mode
(AC mode)
±0.1% of
reference
normal
non-linear
frequency in
Battery mode
Humidity
<95%
1500
2000
91%
Output
Overload capacity
102%-130% load
transfers to Bypass
mode after 2 minutes
(Linear
>130% load transfers
Load)/
to Bypass mode after
<5% for
30 second and
shutdown the output
after 1 minute
load
Altitude
<1000m
2500
3000
3500
86%
82%
78%
49
Current
crest ratio
3:1
maximum
Storage temperature
0°C-40°C
4000
4500
5000
74%
70%
67%