neutral conductor should be provided in the building wiring
installation.
This is permanently connected equipment , it must be installed
★
by qualified maintenance personnel.
For permanently connected equipment: make sure that a
★
readily accessible disconnect device is incorporated in the
building installation wiring.
To reduce the risk of fire, connect only to a circuit provided with
branch circuit overcurrent protection with an ampere rating in
accordance with the IEC/EN 60934 standard or your local
electrical code and have a contact air gap of at least 3 mm.
Uninterruptible power supply
You can connect four extended battery module to the
★
uninterruptible power supply.
Earth connection is essential before connecting to the building
★
wiring terminal.
2.2 Operation
Do not disconnect the earth conductor cable from the UPS or the
★
building wiring terminals in any time since this would cancel the
protective earthing of the UPS system and all connected loads.
The UPS output terminal block may be electrically active even if
★
the UPS system is not connected to the building wiring terminal.
In order to completely disconnect the UPS, firstly press the OFF
★
button, then disconnect the mains lead.
Ensure that no liquid or other foreign objects can enter the UPS.
★
output power
6K
10K
2-pole circuit breaker
2-pole circuit breaker
5
240V
40 amp
63 amp