Fireplace hearth requirements: (Measured without the insert)
The non-combustible fi replace hearth must be raised 50mm above an adjacent combustible fl oor and extend 400mm in front
and 200mm beyond each side of the existing fi replace opening. A non-combustible hearth that extends a minimum 600mm in
front of the fi replace opening may be fl ush to an adjacent combustible fl oor.
MINIMUM FIREPLACE
OPENING AND HEARTH
DIMENSIONS
533mm
200mm
Ember protection:
**
Combustible fl oor in front of the fi replace insert must be protected from hot embers by non-combustible material extending
400mm to the fi ring side from the door and 200mm to other sides of the unit.
MINIMUM EMBER
PROTECTION
DIMENSIONS
Non-combustible fi replace
hearth
Non-combustible fl oor
covering
ALT5.ASCINSB 150714-24
622mm
607mm
Non-combustible fi replace
464mm
200mm
50mm
572mm
**
400mm
400mm
hearth
*
51mm
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
457mm
50mm
9