INSTALLATION AND OPERATING TESTED and LISTED GUIDE to ULC S628 / UL 1482 Meets the U.S. Environmental Protection Model Agency's July 1990 Particulate Emission Standards PACIFIC INSERT Design - D 010203-16 5055.101 PACINSD1...
Safety Clearances READ ALL INSTRUCTIONS BEFORE INSTALLING Masonry or Factory Built Fireplace AND USING THIS APPLIANCE. The minimum required clearances to surrounding combustible We strongly recommend that smoke detectors be installed. If materials when installed into a masonry or factory built fire- smoke detectors have been previously installed, you may place are listed below and in figure #1.
Consult local codes. WARNING: Do not remove bricks or mortar from your Pacific Energy highly recommends the use of a full liner as existing fireplace. the safest installation and providing optimum perform- Exception: Masonry or steel, including the damper plate, may ance.
Into a Factory Built Fireplace ney. Direct Flue Connection Your Pacific Insert may be installed into a factory built fireplace with the following requirements: 1) Measure from the first chimney flue liner to the top of the 1) Inspect your fireplace for damage or other physical de- Insert.
Surround Assembly and Installation Fig. # 7 Fig. # 6 1) Lay part A, B and C face down on a flat non-marring surface. Fasten together with 1/4" x 1/2" bolts and nuts provided through holes at points “D” (Fig. #5 and 8). 2) Lift the surround assembly to the upright position and Brass Trim make sure the front face is flat and even at the joints.
Page 7
9) Push the entire appliance back until the surround assembly Fig. # 10 is in contact with the fireplace. 10) Position the decorative bay stove top onto the firebox top. Ensure that the studs align with the slotted tabs, one on each side of the firebox top.
Combustion Air Fig. # 15 Front Cover Consult local building codes regarding combustion air supply. Intake or combustion air can be supplied to the Insert in one of two ways: 1) Outside air supply: Remove cover from ash clean out in existing fireplace.
Failure to do so may create a hazardous Burns condition. Your Pacific Energy heater is designed for maximum overall 1) Open door and rake hot embers towards the front of the efficiency at a moderate firing rate. Overfiring is hazardous heater.
5) To achieve maximum firing rate, set control to "H" (high). Disposal of Ashes Do not use this setting other than for starting or preheating fresh fuel loads. Ashes should be placed in a metal container with a tight fitting lid.
Chimney fires are dangerous. Chimney inside temperatures can exceed 2000 degrees F. This causes much higher than The Pacific Insert comes equipped with a variable speed normal temperatures in the chimney and on its exterior sur- circulating air blower. The blower system is thermostatically...
Only if this is not possible should you remove baffle assembly. 4. DOOR GASKET - The gasket used by Pacific Energy requires only light pressure to seal. This will prolong seal DO NOT OPERATE WITH BAFFLE ASSEMBLY OR IN- life.
42 3/4" wide x 29" high ** Over-Size Surround Assembly, Plain Panels ... 44 3/8" wide x 33" high Fig. # 18 All parts may be ordered from your nearest Pacific Energy dealer. Contact Pacific Energy for the location of the dealer nearest you.
Appendix A Understanding & Operating Your Pacific Energy Stove The Pacific Energy SUPER SERIES line of Active flaming takes place during the first part of the woodstoves is a culmination of years of research and burn. During this storage, heat is stored in the mass development.
Label LISTED FACTORY BUILT FIREPLACE ACCESSORY INSERT CERTIFIED FOR USE IN CANADA AND U.S.A. MODEL: PACIFIC INSERT SERIES: D TESTED TO: ULCS628 / UL1482 REPORT NO: 5223 (MAY 1989) INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURERíS INSTALLATION AND OPERATING INSTRUCTIONS.
Page 16