Communicating with PanelView 900t Terminals on a DeviceNet Network
Configuring DeviceNet Communications
DeviceNet communication parameters are accessed from the
Terminal Setup dialog. To open the Terminal Setup dialog, choose
Terminal Setup from the PanelBuilder Application menu.
7. Click the Comms. Setup button from the Terminal Setup dialog.
8. Under Terminal, edit the following parameters:
Specify
Node Address
Baud Rate
9. Under I/O Scanner, edit the following parameters:
Specify
Input Size
Output Size
To
Select the address (0 to 63) of the PanelView
terminal on the DeviceNet link.
Select the baud rate of the DeviceNet link. The
available baud rates are:
125 kbps
250 kbps
500 kbps
To
Specify the number of words (from 0 to 64) that
are sent to the scanner from the PanelView with
each I/O message. 0 is the default value which
indicates that no input I/O data exists in the
application.
Specify the number of words (from 0 to 64) that
are received by the PanelView from the scanner
with each I/O message. 0 is the default value
which indicates that no output I/O data exists in
the application.
Publication 2755-6.8
17–9