Vitotronic 100, GC1B Installation and Service
Connecting the Control Unit to the LON
All coding addresses in the table are listed in the "General" group.
Boiler control unit
A
Legend
A Terminal end resistor
Participant no. 1.
Code "77:1".
Control unit is fault
manager.
Code "79:1".
Control unit transmits
the time.
Code "7B:1".
Control unit transmits
outside temperature.
Set code "97:2".
Viessmann system
number.
Code "98:1".
LON participant fault
monitoring
Code "9C:20".
Vitotronic 200-H
Participant no. 10.
Code "77:10".
Control unit is not fault
manager.
Code "79:0".
Control unit receives the
time.
Set code "81:3".
Control unit receives
outside temperature.
Set code "97:1".
Viessmann system
number.
Code "98:1".
LON participant fault
monitoring
Code "9C:20".
The LON communication module (accessory) must be
plugged in.
Installation Instructions
LON communication module
Note: The data transfer via LON can take several minutes.
Single boiler system with Vitotronic 200-H and
Vitocom 100 LAN 1 (example)
Set the LON participant numbers and further functions
via code 2 (see the following table).
Note: In the same LON system, the same participant
number must not be allocated twice.
Only one Vitotronic may be programmed
as fault manager.
Vitotronic 200-H
Participant no. 11.
Set code "77:11".
Control unit is not fault
manager.
Code "79:0".
Control unit receives the
time.
Set code "81:3".
Control unit receives
outside temperature.
Set code "97:1".
Viessmann system
number.
Code "98:1".
LON participant fault
monitoring
Code "9C:20".
Commissioning
Vitocom
A
Participant no. 99.
Device is fault manager.
Device receives the time.
--
--
--
79