120V External Connection - Viessmann VITOTRONIC 100 GC1B Installation And Service Instructions Manual

Digital boiler control unit for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Vitotronic 100, GC1B Installation and Service

120V External Connection

120V pumps with an amperage draw of <2FLA
Legend
A DIN rail
B Pump
120V pumps with an amperage draw of >2FLA
Contactor specification 120VAC 1A
Legend
A DIN rail
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
240V single phase pumps
Contactor specification 120VAC 1A
Legend
A DIN rail
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
208/460/575V 3 phase pumps
Contactor specification 120VAC 1A
Legend
A DIN rail
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
Installation Sequence