Vitotronic 100, GC1B Installation and Service
Matching the Coding Addresses to the System Version
Matching the Control Unit to the Two-stage Burner
Matching coding addresses according to the burner used
Address
03:__
08:__
09:__
0A:__
Matching the Control Unit to the Modulating Burner
Note: The burner must be fully adjusted. To achieve a
wide modulating range, set the minimum output as
low as possible (take the chimney and flue system
into account).
Matching coding addresses according to the burner used
Address Meaning
03:__
Fuel
08:__
Units and tens of the maximum burner
output
09:__
Hundreds of the maximum burner output Example: Max. burner output: 225 kW – select: 2
15:__
Modulation range runtime
0A:__
Ratio of output base load to maximum
burner output in percent
05:__
Ratio of partial output at g of the
servomotor runtime to maximum burner
output in percent
Meaning
Fuel
Units and tens of the maximum
burner output
Hundreds of the maximum burner
output
Ratio of output burner stage 1 to
maximum burner output in percent
Setting
Gas operation: 0 (delivered condition)
Oil operation: 1 (irreversible)
Example: Max. burner output: 225 kW – select: 25
Note: Values up to and including 199 kW can be entered directly.
Calculate servomotor runtime(s) between base load and max.
burner output
Example: Output burner stage 1
135 kW
Max. burner output: 225 kW (135 kW: 225 kW) · 100% = 60%
Example: Partial output 171 kW
Max. burner output: 225 kW (171 kW: 225 kW) · 100% = 76%
Commissioning
(continued)
Setting
Gas operation: 0 (delivered condition)
Oil operation: 1 (irreversible)
Example: Max. burner output:
225 kW – select: 25
Note: Values up to and including 199
kW can be entered directly.
Example: Max. burner output: 225
kW – select: 2
Example: Output burner stage 1
135 kW
Max. burner output: 225 kW
(135 kW: 225 kW) · 100% = 60%
77