Coding Level 2

Category 2 "Boiler"

Coding
Coding in the Delivered Condition
01:1
Single boiler system.
02:1
Two-stage burner.
03:0
Gas operation.
04:...
Switching hysteresis, burner:
Delivered condition specified by the boiler
coding card.
05:...
Modulating burner:
Burner curve.
Delivered condition specified by the boiler
coding card.
06:87 Maximum limit of the boiler water
temperature set to 189°F (87°C).
07:1
Sequential boiler number in a multi boiler
system (in conjunction with coding address
"01").
08:...
Maximum burner output in kW.
Delivered condition specified by the boiler
coding card.
09:...
Maximum burner output in kW.
Delivered condition specified by the boiler
coding card.
0A:...
Burner base load in kW.
Delivered condition specified by the boiler
coding card.
106
Vitotronic 100, GC1B Installation and Service
Possible Change
01:2
Multi boiler system with cascade control
via LON (e.g. Vitotronic 300-K, type MW1B).
01:3
Multi boiler system with on site cascade control
(third party control unit) via switching contacts
(input avD and avH) or 0 – 10V input.
02:0
Single stage burner.
02:2
Modulating burner.
03:1
Oil operation (irreversible).
03:2
Set automatically if no boiler coding card
or an incorrect boiler coding card is inserted.
04:0
Switching hysteresis 4 K (see page 95)
04:1
Switching hysteresis, heat demand-dependent
(see page 95).
ERB50 function (values from 6 to 12 K).
04:2
ERB80 function (values from 6 to 20 K).
05:0
Linear burner curve.
05:1
Non-linear burner curve.
to
(P
: P
)·100
T
max
05:99
P
in kW: Partial output at g of the servomotor
T
runtime
P
in kW: Maximum output.
max
06:20
Maximum limit adjustable from 68 to 260°F
to
(20 to 127°C).
06:127
Observe the adjustable high limit settings.
07:2
Consecutive boiler number in multi boiler system.
to
07:4
08:0
Maximum output adjustable from 0 to 199 kW.
to
08:199
09:0
Maximum output adjustable from 0 to 19,900 kW;
to
1 step
100 kW.
09:199
0A:0
Non-linear burner curve
to
(P
:P
)·100%
G
max
0A:100
P
in kW: Base output
G
P
in kW: Maximum output.
max