Viessmann VITOTRONIC 100 GC1B Installation And Service Instructions Manual page 105

Digital boiler control unit for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Vitotronic 100, GC1B Installation and Service
Category 1 "General"
Coding in the Delivered Condition
5F:0
Function input DE3 at extension EA1:
Not assigned.
6C:0
Run-on time for circulation pump,
neutralizing system at output A1 at
extension AM1: None.
6d:0
Run-on time for circulation pump,
neutralizing system at output A2 at
extension AM1: None.
6E:50
Do Not Adjust.
76:0
Without LON communication module.
77:1
LON participant number.
78:1
LON communication enabled.
79:0
Control unit is not fault manager.
80.6
A fault message is issued if a fault occurs
for at least 30 sec.
88:0
Temperature displayed in °C (Celsius).
8A:175
Do Not Adjust.
8b:0
Do Not Adjust.
8F:0
Do Not Adjust.
93:0
Fault messages during emissions test
function/service display do not affect
central fault messages.
94:0
System with low loss header:
Primary circuit pump and DHW tank
primary pump always run when there is
demand.
95:0
Without Vitocom 100 communication
interface.
98:1
Viessmann system number (in conjunction
with monitoring several systems via
Vitocom 300).
9b:0
No set minimum boiler water temperature
for external demand.
9C:20
Monitoring LON participants:
If there is no response from a participant,
values defaulted by the control unit are
used 20 min. later, and a fault message is
issued.
9d:0
Do Not Adjust.
(continued)
Possible Change
5F:1
5F:2
5F:3
5F:4
5F:5
5F:6
6C:1
to
6C:255
6d:1
to
6d:255
--
76:1
77:1
to
77:99
78:0
79:1
80:0
80:2
to
80:199
88:1
--
--
--
93:1
94:1
94:2
95:1
98:1
to
98:5
9b:0
to
9b:127
9C:0
9C:5
to
9C:60
--
Not assigned.
External demand with set minimum boiler water
temperature.
Set value selected in coding address "9b".
External blocking.
External blocking with fault message input.
Fault message input.
Not assigned.
Run-on time adjustable from 1 to 255 sec.
Run-on time adjustable from 1 to 255 sec.
--
With LON communication module; automatic
recognition.
LON participant number, adjustable from 1 to 99.
Note: Allocate each number only once.
LON communication disabled.
Control unit is fault manager.
Immediate fault message.
The minimum fault duration until a fault message is
issued is adjustable from 10 to 995 sec.;
1 step
5 sec.
Temperature displayed in °F (Fahrenheit).
--
--
--
Fault messages during emissions test function/
service display affect central fault messages.
Primary circuit pump only runs when there is
demand if the burner is running (with run-on time).
DHW tank primary pump only runs when there is
demand if the burner is running (with run-on time).
With Vitocom 100 communication interface;
automatic recognition.
System number adjustable from 1 to 5.
Set value for external demand adjustable from 32
to 260°F (0 to 127°C) (limited by boiler specific
parameters).
No monitoring.
Time adjustable from 5 to 60 min.
--
Coding Level 2
105