Vitotronic 100, Gc1B With 30% Ltp Package (Vd2 Only) - Viessmann VITOTRONIC 100 GC1B Installation And Service Instructions Manual

Digital boiler control unit for use with boiler models vd2a, vd2 and ct3
Table of Contents

Advertisement

Installation Sequence
Vitotronic 100, GC1B with 30% LTP Package
30% LTP Package consists of:
- 1 circulation pump
- 1 cast iron flange set
- 2 full port ball valves
- 1 flow check valve
- 1 17B sensor (strap -on)
Legend
A Vitotronic 100 control
B Junction box
C Return temperature 2 aJB
D Return temperature 1 aJA
E Shunt pump sÖA1
F Boiler pump sL
60
Vitotronic 100, GC1B Installation and Service
(VD2 only)
Each pump output: 120V single phase
Max. pump current: 2 FLA
IMPORTANT
Pump current larger than 2 FLA will require a contactor
or isolation relay (see page 55).
Mandatory Coding Address Changes
0C:5 - Modulating isolation valve
(independant of boiler water temperature).
0d:2 - Switching contact
4A:1 - 17A Sensor installed
4b:1 - 17B Sensor installed
4C:2 - Connections at plug 20A1
Therm-control switch contact
4d:2 - Boiler circuit pump