Vitotronic 100, GC1B Installation and Service

Category 3 "DHW"

Coding
Coding in the Delivered Condition
55:0
DHW tank heating, hysteresis ± 2.5 K.
56:0
Set DHW temperature adjustable from 50 to
140°F (10 to 60°C).
58:0
Without auxiliary function for DHW heating.
59:0
DHW tank heating:
Start point: Set value −2.5 K
Shutdown point: Set value +2.5 K
5A:0
For DHW heating:
The set boiler water temperature is determined
by the highest system supply temperature
demand.
60:20
During DHW heating, the boiler water
temperature is up to 20 K higher than the set
DHW temperature.
61:1
The circulation pump for DHW tank heating
is started immediately.
62:10
Circulation pump with a run-on time after DHW
tank heating of up to 10 min.
63:0
Without auxiliary function for DHW heating.
67:40
For solar DHW heating:
Set DHW temperature 104° F (40° C).
Reheating is suppressed above the selected set
temperature (DHW heating by the boiler only if
solar energy is not sufficient).
68:8
With 2 DHW tank temperature sensors (code
"55:2"):
DHW tank heating stop point at set value x 0.8.
69:7
With 2 DHW tank temperature sensors (code
"55:2"):
DHW tank heating start point at set value x 0.7.
6A:75
Runtime, servomotor, mixing valve, heat
exchanger set, Vitotrans 222, 80 and 120 kW:
75 sec.
Possible Change
55:1
Adaptive DHW tank heating enabled (see page 96).
55:2
DHW tank temperature control with 2 DHW tank
temperature sensors (see page 97).
55:3
DHW tank temperature control, primary store
system (see page 97).
56:1
Set DHW temperature adjustable from 50 to
203°F (10 to 95°C).
Note: Observe the max. permissible DHW
temperature. Reset the adjustable high
limit "R".
58:1
Input of a second set DHW temperature,
to
adjustable from 34 to 203°F (1 to 95°C).
58:95
(observe coding address "56").
59:1
Start point adjustable from 1 to 10 K below
to
the set value.
59:10
5A:1
For DHW heating:
The set boiler water temperature is determined
by the DHW tank supply temperature demand.
60:5
The differential between the boiler water
to
temperature and the set DHW temperature is
60:50
adjustable from 10 to 50 K.
61:0
The circulation pump for DHW tank heating is
started depending on the boiler water temperature.
62:0
Circulation pump without run-on.
62:1
Run-on time adjustable from 1 to 15 min.
to
62:15
63:1
Auxiliary function: 1 x daily.
63:2
Every 2 days to every 14 days.
to
63:14
63:15
2 x daily.
67:0
Set DHW temperature adjustable from 32 to
to
203°F (0 to 95°C). (limited by boiler-specific
67:95
parameters).
68:2
Factor adjustable from 0.2 to 1;
to
1 step
0.1.
68:10
69:1
Factor adjustable from 0.1 to 0.9;
to
1 step
0.1.
69:9
6A:10
For heat exchanger set
to
Vitotrans 222, 240 kW: set 113 sec.
6A:255
Runtime adjustable from 10 to 255 sec.
Coding Level 2