Rack Installation/Removal Of Server - Fujitsu PRIMERGY RX600 S4 Operating Manual

Hide thumbs Also See for PRIMERGY RX600 S4:
Table of Contents

Advertisement

Hardware installation
4.2

Rack installation/removal of server

V
CAUTION!
Follow the safety instructions and the rack installation instructions in
chapter
At least two people are needed to position the server into/out of the
rack.
The rack may tip over if more than one unit is removed at the same
time.
Rack requirements
The rack systems from Fujitsu Siemens Computers (PRIMECENTER Rack,
DataCenter Rack) ideally support installation of PRIMERGY server systems.
Installation in the currently standard rack systems of various manufacturers (3rd
party rack) is possible in so far as they support the
EIA-310-D standard for 19 inch racks.
I
The Classic Rack is not supported for the PRIMERGY RX600 S4.
To accommodate the ventilation concept and ensure proper ventilation, any
unused areas in the rack must be sealed using dummy covers.
The power is supplied via the multiple socket outlets fitted in the rack.
The main features of the rack systems from Fujitsu Siemens Computers are as
follows:
PRIMECENTER Rack
– In connection with so-called assembly brackets frontally bolted telescopic
rails or sliding rails.
Two of these assembly brackets and/or the sliding rails are provided with a
linear alignment possibility to ensure also an adjustment to different rack
depths.
– Enhanced cable management in the lateral rack area.
RX600 S4
"Important information" on page
Operating manual
Rack installation/removal of server
23.
39

Advertisement

Table of Contents
loading

Table of Contents