3.12.2 Parameter setting / download via tool

Control parameters can be adjusted via bus either by parameter download during
commissioning or during normal operation with a tool like ACS700.
With the ACS700 tool, the parameters can be changed...
– during commissioning via parameter download (all parameters)
– during normal operation via Popcard (most of the parameters)
Most parameters can be changed during normal operation using the OZW772 web
server or the RMZ792 bus operator unit.
Only the parameters for device address can be downloaded via ETS3 Professional.
This is to simplify and avoid a conflict.
It allows you to further engineer communication objects of an RDG previously
commissioned vial local HMI or ACS (assigning communication objects to group
addresses).
 The basic application can only be changed via parameter download with ACS.
 The RDG KNX thermostats require version ETS3f or higher / ACS700 version
5.11 or higher.
Connecting a KNX commissioning / operating tool to the RDG is described in
section 4.2.
RDG400KN Basic documentation
Functions
CE1P3192en
20 Jul 2010