Siemens RDG400KN Basic Documentation page 38

Room thermostat with knx communications
Hide thumbs Also See for RDG400KN:
Table of Contents

Advertisement

Setting the sequence and the control outputs
38 / 78
Siemens
Building Technologies
Without a valid bus signal for changeover air, the air volume is only increased for
cooling:
2-position heating / cooling coil
Y
100%
Vmax
Vmin
0%
Changeover water
Y
SDH
H
ON
YHC
w
OFF
dz
Y
Output signal
TR
Room temperature
w
Comfort setpoint if changeover water = Heating
(w)
Comfort setpoint if changeover water = Cooling
H
Heating sequence
C
Cooling sequence
YV
Volume flow rate
Note: The diagrams show the PI controller's proportional part only.
Refer to sections 3.4 "Applications", 3.6.1 "Sequences", and 3.7 "Outputs".
RDG400KN Basic documentation
Functions
Modulating heating / cooling coil
XpC
C
100%
Vmax
YV
Vmin
0%
TR [°C]
SDC
C
100%
YHC
(w)
0%
TR [°C]
XpH
XpC
Vmin
Vmax Maximum volume output
Y
XpC
Changeover water
Y
XpH
H
YHC
w
dz
Proportional band heating
Proportional band cooling
Minimum volume output
CE1P3192en
20 Jul 2010
C
YV
TR [°C]
XpC
C
YHC
(w)
TR [°C]