Operation; Front Display - Allen-Bradley 1609-P3000N User Manual

3000/5000 va ups; tower/rack-mount 3u uninterruptible power supply
Hide thumbs Also See for 1609-P3000N:
Table of Contents

Advertisement

O
PERATION
Load
Indicator
Description
The Online LED illuminates when the UPS is drawing utility power and performing
Online
double conversion to supply power to connected equipment.
The UPS is supplying battery power to the connected equipment.
On Battery
The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility
Bypass
power is sent directly to connected equipment during bypass mode operation.
Bypass mode operation is the result of an internal UPS fault, an overload condition
or a user initiated command either through an accessory or the manual bypass
switch. Battery operation is not available while the UPS is in bypass mode. Refer to
Troubleshooting in this manual.
The UPS detects an internal fault.
Fault
Refer to Troubleshooting in this manual.
An overload condition exists. See Troubleshooting.
Overload
The battery is disconnected or must be replaced. See Troubleshooting.
Replace
Battery
Feature
Function
Press this button to turn on the UPS. (See below for additional capabilities.)
Power On
Press this button to turn off the UPS.
Power Off
F
D
RONT
ISPLAY
7
Battery Charge