Online Led - Allen-Bradley 1609-P3000N User Manual

3000/5000 va ups; tower/rack-mount 3u uninterruptible power supply
Hide thumbs Also See for 1609-P3000N:
Table of Contents

Advertisement

P
P
ROBLEM AND
OSSIBLE
C
AUSE
LED
BYPASS
ILLUMINATES
The bypass switch has been
turned on manually or through
an accessory.
FAULT AND OVERLOAD
The UPS has ceased sending
power to connected equipment.
LED
FAULT
ILLUMINATES
Internal UPS fault.
LED
REPLACE BATTERY
Replace Battery LED flashes and
short beep is emitted every two
seconds to indicate the battery is
disconnected.
Weak battery.
Failure of a battery self-test.
UPS
OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
Very high, low, or distorted line
voltage. Inexpensive fuel
powered generators can distort
the voltage.
D
U
V
IAGNOSTIC
TILITY
All five LEDs are illuminated
There is no LED illumination
O
LED
NLINE
There is no LED illumination
The LED is blinking
If bypass is the chosen mode of operation, ignore the illuminated LED.
If bypass is not the chosen mode of operation move the bypass switch on the
back of the UPS, to the normal position.
LED
, UPS
S ILLUMINATE
The connected equipment exceeds the specified "maximum load" as defined in
Specifications section of the Quick Start Guide.
Disconnect nonessential equipment from the UPS to eliminate the overload
condition.
Press the OFF button, then the ON button to restore power to connected
equipment.
Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
ILLUMINATES
Check that th e battery connectors are fully engaged.
Allow the battery to recharge for 24 hours. Then, perform a self-test. If the
problem persists after recharging, replace the battery.
The UPS emits short beeps for one minute and the Replace Battery LED
illuminates. The UPS repeats the alarm every five hours. Perform the self-test
procedure after the battery has charged for 24 hours to confirm the Replace
Battery condition. The alarm stops and the LED clears if the ba ttery passes the
self-test.
Move the UPS to a different outlet on a different circuit. Test t he input voltage
with the utility voltage display.
OLTAGE
The line voltage is extremely high and should be checked by an electrician.
If the UPS is plugged into a properly functioning utility power outlet, the line
voltage is extremely low.
The UPS is running on battery, or it is not turned on.
The UPS is running an internal self-test.
S
OLUTION
EMITS A SUSTAINED ALARM TONE
15