Allen-Bradley 1609-P3000N User Manual page 10

3000/5000 va ups; tower/rack-mount 3u uninterruptible power supply
Hide thumbs Also See for 1609-P3000N:
Table of Contents

Advertisement

U
C
SER
ONFIGURABLE
N
OTE
F
UNCTION
Automatic Self-Test
UPS ID
Date of Last Battery
Replacement
Minimum Capacity
Before Return from
Shutdown
Alarm Delay After
Line Failure
Shutdown Delay
Duration of
Low Battery Warning.
Synchronized Turn-on
Delay
High Bypass Point
I
TEMS
: S
ETTINGS ARE MADE THROUGH SUPPLIED
N
M
OPTIONAL
ETWORK
F
ACTORY
D
EFAULT
Every 14 days
(336 hours)
UPS_IDEN
Manufacture Date
0 percent
5 second delay
20 seconds
2 minutes
PowerChute
software provides
automatic,
unattended
shutdown when
approximately 2
minutes of battery
operated runtime
remains.
0 seconds
+10% of
output voltage
setting
P
OWER
,
ANAGEMENT CARDS
OR
U
S
SER
ELEC TABLE
C
HOICES
Every 7 days(168 hours),
14 days (336 hours)
On Startup Only,
No Self-Test
Up t o eight characters to
define the UPS
Date of
Battery Replacement
mm/dd/yy
0, 15, 25, 35, 50, 60, 75,
90 percent
5 or 30 second delay
At Low Battery
Never
0, 20, 60, 120, 240, 480,
720, 960 seconds
2, 5, 7, 10, 12, 15, 18,
20 minutes
0, 20, 60, 120, 240, 480,
720, 960 seconds
+5%, +10%, +15%,
+20%
9
C
,
HUTE SOFTWARE
T
M
.
ERMINAL
ODE
D
ESCRIPTION
Set the interval at which the
UPS will execute a self-test.
Uniquely identify the UPS, (i.e.
server name or location) for
network management purposes.
Reset this date when you replace
the battery modules.
Following a low-battery
shutdown, the battery modules
will be charged to the specified
percentage before powering
connected equipment.
Mute ongoing alarms or disable
all alarms permanently.
Set the interval between the time
when the UPS receives a
shutdown command and the
actual shutdown.
The low battery warning beeps
are continuous when two
minutes of run time remain.
Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
The UPS will wait the specified
time after the return of utility
power before turn-on (to avoid
branch circuit overload).
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.