Wiring and Connecting the UPS
C
UPS
ONNECTING
USING POWER CORD
1609-P3000N – Use captive 8 ft cord. NEMA L5-30 Plug is attached to this cord.
1609-P3000H – Use in captive 8 ft cord. NEMA L6-30 Plug is attached to this cord.
1609-P3000A – User must supply power cord. Power cord must mate with IEC 320 C20 inlet.
H
I
ARDWIRING
NSTRUCTIONS
Wiring must be performed by a qualified electrician.
Install a high magnetic 30/32 A utility circuit breaker,
(Allen-Bradley Catalog Number 1489-A2C300).
Adhere to all national and local electrical codes.
Use #10 AWG gauge (5 sq. mm) wire.
1.
Switch the utility circuit breaker OFF.
2.
Remove the input access panel.
3.
Remove circular knockout.
4.
Run #10 AWG gauge (5 sq. mm) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral).
Use an appropriate strain relief (not included).
5.
Switch the utility circuit breaker ON.
6.
Check line voltages.
7.
Replace the access panel.