Troubleshooting; Front Panel Led - Allen-Bradley 1609-P3000N User Manual

3000/5000 va ups; tower/rack-mount 3u uninterruptible power supply
Hide thumbs Also See for 1609-P3000N:
Table of Contents

Advertisement

T
ROUBLESHOOTING
P
P
ROBLEM AND
OSSIBLE
C
AUSE
UPS
WILL NOT TURN ON
Battery not connected pro perly.
button not pushed.
UPS not connected to utility
power supply.
Very low or no utility voltage.
UPS
WILL NOT TURN OFF
button not pushed.
Internal UPS fault.
UPS
BEEPS OCCASIONALLY
Normal UPS operation when
running on battery.
UPS
DOES NOT PROVIDE EXPECTED BACKUP TIME
The UPS battery(s) are weak
due to a recent outage or
battery(s) are near the end of
their service life.
LED
FRONT PANEL
S FLASH SEQUENTIALLY
The UPS has been shut down
remotely through software or an
optional accessory card.
LED
ALL
S ARE OFF AND THE
The UPS is shut down and the
battery is discharged from an
extended outage.
BYPASS AND OVERLOAD
The UPS is overloaded
Check that the battery connectors are fully engaged.
Press the
Check that the power cable from the UPS to the utility power supply is securely
connected at both ends.
Check the utility power supply to the UPS by plugging in a table lamp. If the
light is very dim, have the utility voltage checked.
Press the
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
None. The UPS is protecting the connected equipment.
Charge the battery(s). Battery modules require recharging after extended outages.
They wear faster when put into service often or when operated at elevated
temperatures. If the battery(s) are near the end of their service life, consider
replacing the battery(s) even if the Replace Battery LED is not illuminated.
None. The UPS will restart automatically when utility power returns.
UPS
IS PLUGGED INTO A WALL OUTLET
None. The UPS will return to normal operation when the power is restored and
the battery has a sufficient charge.
LED
, UPS
S ILLUMINATE
The connected equipment exceeds the specified "maximum load" as defined in
Specifications section of the Quick Start Guide.
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.
S
OLUTION
button once to power the UPS and the connected equipment.
button once to turn the UPS off.
EMITS A SUSTAINED ALARM TONE
14