Installation of the Condensate Pipe
1) The condensate pipe should keep a inclination angle of 5~10°, which can facilitate the drainage of the
condensate water. And the joints of the condensate pipe should be insulated by the insulation material
to prevent condensing.
2) There is a condensate outlet on both left and right sides of the unit. Once one is confirmed to be used,
the other should be clogged by a rubber plug, bundled by the binding wire and insulated by the
insulation material to avoid water leakage.
3) The right outlet is defaulted to be clogged with a plug.
CUATION!
No water leakage is allowed on the joint of the condensate pipe.
4.2.11
Design of the Drain Pipe
1) The drain pipe should always keep an inclination angle(1/50~1/100) to avoid the water gathering in
some certain place.
2) During the connection of the drain pipe and device, do not impose too much force on the pipe on one
side of the device and the pipe should be fixed as close as to the device.
3) The drain pipe can be the ordinary hard PVC pipe which can be purchased locally. During the
connection, inset the end of the PVC pipe to the drain outlet, then tighten it with the drain hose and
binding wire but never connect the drain outlet and the drain hose by adhesive.
4)
When the drain pipe is used for multiple devices, the public section of the pipe should be 100mm lower
than the drain hole of each device and it is better to use the much thicker pipe for such a purpose.