Contents PRODUCT ........................2 MODELS LIST ........................2 Outdoor Unit ..........................2 BU Module..........................2 Indoor Unit..........................3 NOMENCLATURE ......................5 Nomenclature of Outdoor Unit ....................5 Nomenclature of BU Module....................5 Nomenclature of Indoor Unit....................5 ...
Page 3
FLOW CHART OF INSTALLATION................67 OUTDOOR UNIT INSTALLATION ................68 3.1 Precautions for R410A......................68 3.2 Precaution for Installation....................68 3.3 Names of Main Parts......................68 3.4 Parts and Components of Unit .....................69 3.5 Selection of Installation Location ..................69 3.6 Outline Dimension of the Outdoor Unit ................70 3.7 Installation and Servicing Space ..................70 3.8 Installation of the Outdoor Unit ...................71 INDOOR UNIT INSTALLATION ...................72...
Page 4
7.8 Electrical Wiring Work for Indoor Unit ................120 INSTALLATION OF DRAINAGE PIPELINE ............121 8.1 Material Quality Requirements for Condensate Pipe ............121 8.2 Key Points for Condensate Pipe Installation..............121 Installation of Protective Layer on Connection Pipe ............125 MAINTENANCE ....................127 Testing Board Introduction .....................127 1.1 Compose of Testing Board....................127 1.2 Instruction of Function and Data Section ................127 1.3 Process Control Setting......................128...
Page 5
Super Free Match Service Manual PRODUCT PRODUCT...
Super Free Match Service Manual PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Cooling Heating Refriger Power supply Model Product code Capacity Capacity Appearance Ph, V, Hz GWHD(42S)NK3 CN860W0070 12.1 12.5 GWHD(48S)NK3 R410A 1,220~240,50 CN860W0080 14.0 15.5 GWHD(56S)NK3 CN860W0090 15.5 17.5 1.2 BU Module Number of connectable Power supply...
Super Free Match Service Manual 3 FUNCTION Wall Cassette Floor Console Function Duct type mounted type ceiling type type Fan operation Mode ● ● ● ● ● Auto Swing Controller ● ● ● ● Timer Selector ● ● ● ● ●...
Super Free Match Service Manual 4 PRODUCT DATA 4.1 Product Data of Outdoor Unit GWHD(42S)NK3 GWHD(48S)NK3 GWHD(56S)NK3 Model Heat pump Cooling capacity 12.1 15.5 Heating capacity 12.5 15.5 17.5 Cooling Nominal input Heating EER/COP 2.95/3.37 2.85/3.60 2.92/3.64 Maximum NO. of connectable indoor units Total capacity index of to be connected indoor units Power supply...
Super Free Match Service Manual 4.2 Product Data of Indoor Unit 4.2.1 Wall mounted Hansol GWH(07)TA-K GWH(09)TA-K GWH(12)TB-K GWH(18)TC-K Model 3DNA1E/I 3DNA1E/I 3DNA1E/I 3DNA1E/I Cooling 2.10 3.50 5.30 Capacity Heating 2.60 2.75 3.65 5.60 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.029...
Page 13
Super Free Match Service Manual U-cool GWH(07)UA-K GWH(09)UA-K GWH(12)UB-K GWH(18)UC-K Model 3DNA1B/I 3DNA1B/I 3DNA1B/I 3DNA1B/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 0.04 0.06 m3/h Air flow volume Sound pressure level 37/35/32/30/28/ 38/35/32/30/28/ 39/37/34/31/29/ 44/40/37/35/33/...
Page 14
Super Free Match Service Manual Cozy GWH(07)MA-K GWH(09)MA-K GWH(12)MB-K GWH(18)MC-K Model 3DNA3E/I 3DNA3E/I 3DNA3E/I 3DNA3E/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 0.04 0.045 Air flow volume Sound pressure level dB(A) 36/34/31/28/- 37/34/31/28/- 38/34/32/30/- 46/43/40/36/-...
Page 15
Super Free Match Service Manual Change GWH(07)KF-K GWH(09)KF-K GWH(12)KF-K GWH(18)KG-K Model 3DNA6E/I 3DNA6E/I 3DNA6E/I 3DNA6E/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 0.03 0.06 Air flow volume Sound pressure level dB(A) 40/38/30/24/- 41/38/30/24/- 42/39/31/25/- 45/40/37/32/-...
Page 16
Super Free Match Service Manual Viola Model GWH(07)RA-K3DNA3E/I GWH(09)RA-K3DNA3E/I Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.03 0.03 Air flow volume Sound pressure level (SH/H/M/L) dB(A) 40/37/35/32/- 40/37/35/32/- Output 0.01 0.01 Fan motor Running current 0.14 0.14 inch 3/8″(Φ9.52mm)
Page 17
Super Free Match Service Manual GWH(12)RB-K3DN GWH(18)RC-K3DN GWH(24)RC-K3DN Model A3E/I A3E/I A1A/I Cooling 6.45 Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.05 0.06 0.065 1000 Air flow volume Sound pressure level dB(A) 42/39/36/33/- 45/42/37/33/- 48/46/44/42/- (SH/H/M/L) Output 0.02 0.02...
Page 18
Super Free Match Service Manual 4.2.2 Duct type GFH(09)EA-K3D GFH(12)EA-K3D GFH(18)EA-K3D Model Heat pump NA1A/I NA1A/I NA1A/I Cooling 2.50 3.50 5.00 Capacity Heating 2.80 3.85 5.50 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.065 0.075 0.08 m3/h Air flow volume Sound pressure level (H/L) dB(A) 37/31...
Page 19
Super Free Match Service Manual Model Heat pump GFH(21)EA-K3DNA1A/I GFH(24)EA-K3DNA1A/I Cooling 6.00 7.10 Capacity Heating 6.60 8.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.11 0.11 m3/h 1000 1000 Air flow volume 588.5 588.5 Sound pressure level dB(A) 42/34 42/34 Output 0.061...
Page 20
Super Free Match Service Manual 4.2.3 Cassette Model Heat pump GKH(12)BA-K3DNA2A/I GKH(18)BA-K3DNA2A/I Cooling 3.50 4.50 Capacity Heating 4.00 5.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input 0.05 0.05 m3/h Air flow volume Sound pressure level(H/L) dB(A) 46/42 46/42 Output 0.011 0.011 Fan motor...
Page 21
Super Free Match Service Manual GKH(12)BA-K3 GKH(18)BA-K3 GKH(24)BA-K3 Model Heat pump DNA1A/I DNA1A/I DNA1A/I Cooling 3.50 5.00 7.10 Capacity Heating 3.85 5.50 8.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.07 0.07 0.10 m3/h 1180 Air flow volume Sound pressure level dB(A) 37/33...
Page 22
Super Free Match Service Manual 4.2.4 Floor ceiling type GTH(09)BA-K3 GTH(12)BA-K3 GTH(18)BA-K3 GTH(24)BA-K3 Model Heat pump DNA1A/I DNA1A/I DNA1A/I DNA1A/I Cooling 2.50 3.50 5.00 7.10 Capacity Heating 2.80 3.85 5.50 8.00 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.055 0.055 0.11...
Page 23
Super Free Match Service Manual 4.2.5 Console type GEH(09)AA-K3DNA1 GEH(12)AA-K3DNA1 GEH(18)AA-K3DNA1 Model Heat pump Cooling Capacity Heating Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input 0.05 0.05 0.05 m3/h Air flow volume Sound pressure level dB(A) 40/38/36/33/30/27/25 42/40/38/37/35/32/25 48/46/44/41/37/35/32 (SH/H/MH/M/ML/L/SL) Output 0.03...
Super Free Match Service Manual 4.3 Product Data of BU Module Model FXA2A-K FXA2B-K FXA3A-K FXA3B-K Maximum numbers of connectable indoor units Power Supply V-Ph-Hz 220~240-1-50 Φ15.9 Φ19.3 Φ15.9 Φ19.3 Gas pipe(inner diameter) Connection port to outdoor Φ9.52 Φ9.7 Φ9.52 Φ9.7 Liquid pipe(inner diameter) unit...
Super Free Match Service Manual 5 Working Temperature Range Indoor side state Outdoor side state Sorts Dry bulb temp. ℃ Wet bulb temp. ℃ Dry bulb temp. ℃ Wet bulb temp. ℃ Rated Cooling Max. cooling Min. cooling — Rated Heating Max.
Super Free Match Service Manual 6 PIPING DIAGRAM Schematic Diagram of Super Free Match Series Inverter Heat Pump Multi System The units start to work once the power is switched on. During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid.
Page 27
Super Free Match Service Manual pressure refrigerant gas again. Such a refrigeration cycle goes round and round to achieve the desired refrigeration purpose. During the heating operation, the four-way valve is involved to make the refrigeration cycle run reversely. The refrigerant radiates heat in the heat exchanger of the indoor unit (so do the electric heating devices) and absorb heat in the heat exchanger of the outdoor unit for a heat pump heating cycle so as to achieve the desired heating purpose.
Page 28
Super Free Match Service Manual CONTROL CONTROL...
Super Free Match Service Manual 1.1 Cooling/Dry Operation Cooling Operation Is there Guide Louver? Guide Louvers Swing Fan Motor:Operation Is the process of preventing restart operation? (3 minutes) Temperature Adjustment Fan Motor: Stop Electronic Expansion Valve: Stop Electronic Expansion Valve:Capacity Conctrol Stop (Go to the previous page) CONTROL...
Super Free Match Service Manual 2 MAIN LOGIC 2.1 Control Function of Outdoor Unit 2.1.1 Cooling Mode Cooling conditions and process: If the compressor is in stop status and start the unit for cooling operation, when one of the indoor units reaches the cooling operation condition, the unit starts cooling operation;...
Super Free Match Service Manual The status of 4-way valve: energized; Outdoor fan control in heating mode The outdoor fan starts before 5s of the starting of compressor and then it will run in high speed for 40s; The fan shall run at every speed for at least 80s; When the compressor stops, the outdoor fan stops after 1min. Defrosting function When the defrosting condition is met, the frequency of the compressor starts to decrease and wait for defrosting;...
Super Free Match Service Manual 2.2.4 Communication malfunction Detection of the quantity of installed indoor units and BU modules: After 3min of energizing, if the outdoor unit does not receive the communication data of certain indoor unit, the outdoor unit will judge that indoor unit is not installed and will treat it as it is not installed.
Super Free Match Service Manual 2.4 Control Function of Indoor Unit 2.4.1 Running Mode 1. COOL 2.DRY 3.HEAT 4.AUTO 5 FAN 2.4.2 Basic Functions of the System COOL Mode Under this mode, the fan and swing function goes as the set conditions, and the set temperature range is 16℃ ~30℃.
Page 36
Super Free Match Service Manual speed. d) Under the HEAT Mode: (Ambient temperature herein is the temperature without temperature compensation) ◆ When the ambient temperature is or lower than the set temperature, the indoor unit runs at the high speed. ◆...
Page 37
Super Free Match Service Manual c) When the indoor unit works without the wired controller, if the timer is not set for the last remote control instruction, the system will memorize this last instruction and works following it; if the timer is set, it will be canceled as the power failure occurs and will have to be reset.
Super Free Match Service Manual 3 REMOTE CONTROLLER 3.1 Wired Remote Controller 3.1.1 Wired Controller XK19 (Z63351L) It is designed for the cassette type, duct type and floor ceiling type indoor units. ◆ Outside View of the Wired Controller ◆...
Page 39
Super Free Match Service Manual Master wired controller (this function is yet unavailable for this unit). It blinks under on state of the unit without operation of any button. Energy-saving function.(this function is yet unavailable for this unit) Ambient/preset temperature value. Electric auxiliary heating function.(this function is yet unavailable for this unit) Blow function.
Page 40
Super Free Match Service Manual 3.1.3 Operation Instructions On/Off Press On/Off to turn on the unit and turn it off by another press. Mode Setting Under the “On” state of the unit, press Mode to switch the operation modes as the following sequence: Cooling-Dry-Fan-Heating.
Page 41
Super Free Match Service Manual b. 26℃ is the default Sleep curve temperature before delivery. The wired controller will automatically memorize the Sleep curve after the setting. Turbo Setting Turbo function: The unit at the high fan speed can realize quick cooling or heating so that the room temperature can quickly approach the setting value.
Page 42
Super Free Match Service Manual failure will resume its original running state upon power recovery. Memory contents: On/Off, Mode, set temperature, set fan speed, Save function and Lock function. Enquiry of the Outdoor Ambient Temperature Under the “On” or “Off” state of the unit, press Enter/Cancel for 5s, and the outdoor ambient temperature will be displayed after a sound of click.
Super Free Match Service Manual 3.2 Wireless Remote Controller YT1F (MOTO) Notes: a. Be sure that there are no obstructions between the receiver and the remote controller; b. Do not drop or throw the remote controller; c. Do not let any liquid into the remote controller and expose the remote controller to direct sunlight or any place where is very hot.
Page 44
Super Free Match Service Manual MODE Auto, Cool, Dry Fan, Heat modes can be selected circularly by pressing this button. Auto mode is the default after power on. Under Auto mode, the temperature will not be displayed. Under Heat mode, the initial value is 28 ℃(82℉);...
Page 45
Super Free Match Service Manual This kind of remoter controller is universal. And the three swing statuses of are the same as that If the swing function is deactivated when the air guide louver is swing up and down, it will stop at the current position indicates that the air guide louver swings up and down among all five positions.
Super Free Match Service Manual 5) Press to select the swing angle. 3.2.3 Guide for Optional Operation About X-FAN This function indicates that moisture in the evaporator of the indoor unit will be dried after the unit is stopped to avoid mould.
Super Free Match Service Manual 3.3 Wireless Remote Controller YAA1FB1 Notes: a. Be sure that there are no obstructions between the receiver and the remote controller; b. Do not drop or throw the remote controller; c. Do not let any liquid into the remote controller and expose the remote controller to direct sunlight or any place where is very hot.
Page 48
Super Free Match Service Manual the LED of the indoor, and the unit will automatically select the suitable operation mode in accordance with the room temperature to make indoor room comfortable. This button is used for setting Fan Speed in the sequence that goes from AUTO, , then back to Auto.
Page 49
Super Free Match Service Manual ◆ Sleep 3- the sleep curve setting under Sleep mode by DIY: ① Under Sleep 3 mode, press "Turbo" button for a long time, remote control enters into user individuation sleep setting status, at this time, the time of remote control will display "1hour ", the setting temperature "88"...
Super Free Match Service Manual 13) T-ON/ T-OFF: Press T-ON button to initiate the auto-ON timer. To cancel the auto-timer program, simply press this button again. After press of this button, disappears and "ON "blinks. 00:00 is displayed for ON time setting. Within 5 seconds, press + or - button to adjust the time value.
Super Free Match Service Manual 3.4 Wireless Remote Controller YAG1FB Notes: a. Be sure that there are no obstructions between the receiver and the remote controller; b. Do not drop or throw the remote controller; c. Do not let any liquid into the remote controller and expose the remote controller to direct sunlight or any place where is very hot.
Page 52
Super Free Match Service Manual Low fan Low-Medium fan Medium fan Medium-High fan High fan Note: It’s Low fan speed under Dry mode. TEMP Press this button, the following temperature can be set circularly: the setting temperature, indoor ambient temperature and outdoor ambient temperature.
Page 53
Super Free Match Service Manual 10) —: Presetting temperature can be decreased. Press this button, the temperature can be button set up, continuously press this button and hold for two seconds, the relative contents can quickly change, until unhold this button and send the order that the ℃(℉) signal will be displayed all the time.
Page 54
Super Free Match Service Manual Press this button once, to turn on the I FEEL function, then the figure of "I FEEL" will be displayed, after every press of other function button, every 200ms to send I FEEL once, after this function started, the remote control will send temperature to the main un it in every 10 minutes.
Super Free Match Service Manual will decrease 1℃ in every hour, after 3℃ decreased, this temperature will be maintained. Sleep 3- the sleep curve setting under Sleep mode by DIY: ① Under Sleep 3 mode, press "Turbo" button for a long time, remote control enters into user individuation sleep setting status, at this time, the time of remote control will display "1hour ", ②...
Page 56
Super Free Match Service Manual unit will be off directly. About AUTO RUN If start this function, the unit will run at super-high fan speed to cool or heat quickly so that the ambient temperature approaches the preset temperature as soon as possible. About lock Press +...
Super Free Match Service Manual fan mode. About Sleep function Under the Fan and Auto mode, the Sleep function cannot be set up, under Dehumidify mode, only Sleep 1 can be selected. Select and enter into any kind of Sleep mode, the Quiet function will be attached and stared, different Quiet status could be optional and turned off.
Page 58
Super Free Match Service Manual Press " " button and " " button can adjust swing angle. After selecting cool mode, air conditioner operates under cool mode. Cool indicator " " on indoor unit is ON. You can press "+" or "-" button to adjust set temperature. Press "FAN" button can adjust ...
Page 59
Super Free Match Service Manual When selecting "with remote controller, it’s auto swing. Horizontal louver of air conditioner will swing up & down automatically at the maximum angle. , When selecting “ ”with remote controller, it’s the fixed position swing.
Page 60
Super Free Match Service Manual When the unit operates under X-FAN mode, press "X-FAN" button can turn off X-FAN function. Indoor fan stops operation immediately. TEMP Press this button can see indoor set temperature, indoor ambient temperature or outdoor ambient temperature on indoor unit’s display.
Page 61
Super Free Match Service Manual displayed. 13) LIGHT Press LIGHT button to turn on the display's light and press this button again to turn off the display's light. If the light is turned on, is displayed. If the light is turned off, disappears.
Super Free Match Service Manual 4 Smart Zone Controller (CE50-24/E) 4.1 General Introduction 4.1.1 Function Introduction This smart zone controller is a kind of regional controller, which is designed for free match units, capable of controlling up to 3 outdoor units and 16 indoor units.
Super Free Match Service Manual 4.2 Communication Network Note: The smart zone controller can connect with maximum up to 3 outdoor units and 16 indoor units. However, the total of the indoor units of all four ports cannot exceed 16. 4.3 LCD 4.3.1 Outline of the LCD ...
Super Free Match Service Manual Name Description Fan speed It displays the fan speed of the indoor unit, high, medium, low and auto. Running mode It displays the running mode of the indoor unit, auto, cool, dry, fan and heat. It displays the current time (hour and minute) in 24-hour time system and also System clock the week day.
Page 65
Super Free Match Service Manual 4.4.2 Introduction to the Function of Buttons Name Function Description Mode It is used for the switchover among different modes. It is used to set the fan speed, high, medium, low or auto. On/Off It is used to set the on/off status of the indoor unit. 1.
Page 66
Super Free Match Service Manual INSTALLATION INSTALLATION...
Super Free Match Service Manual INSTALLATION 1 PRECAUTIONS FOR INSTALLATION 1.1 Precautions for Installation Before installation, please ensure the installing site, power ratings, possible operating range (pipe distance, height difference between indoor and outdoor unit, power voltage) and installing space are correct and suitable. To ensure correct installation, please make sure to read the Safety Considerations thoroughly before starting the installation works.
Page 68
Super Free Match Service Manual Do not use or store flammable, explosive, poisonous or other dangerous substances beside the air conditioner. When installing or relocating the unit. Please contact the appointed service center or the professional installation personnel for the repair or relocation of the unit. The compressor will vibrate sharply if the voltage is too low and damage the refrigerating system.
Super Free Match Service Manual 1.2 Key Points of Installation Installation Procedures Description and Acceptance Criteria ◆ The materials specified on the engineering drawing shall be purchased as specified (e.g. copper tube, thermal insulation tube, PVC pipe, power cables, air switch, etc). ◆...
Page 70
Super Free Match Service Manual ◆ Purge the system clean. ◆ Keep the pressure for 24 hours Purge and make leakage ◆ Except for the influence by temperature, it is deemed detection under pressure acceptable if pressure drop is within 0.02MPa. (With the temperature change by 1 , the pressur ℃...
Super Free Match Service Manual 2 FLOW CHART OF INSTALLATION Design kicking-off Material selection Inspection of site installation position Installation of indoor unit Installation of outdoor unit Installation of BU module Installation of Connection of Connection of Connection of Connection of Connection of remote transmission...
Super Free Match Service Manual 3 OUTDOOR UNIT INSTALLATION 3.1 Precautions for R410A It is very strict that the refrigerant pipes should be clean and dry. The R410A is a mixed refrigerant, when add the refrigerant to the unit, it must keep the refrigerant in its liquid state.
Super Free Match Service Manual 3.4 Parts and Components of Unit For the super free match series system, one outdoor unit is able to drive up to three BU modules and nine indoor units which include cassette type, duct type, wall mounted type, floor ceiling type and console type. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stop once the outdoor unit is turned off.
Super Free Match Service Manual mounting surface must be horizontal plane. There is enough space for the installation and maintenance. The place should be well-ventilated, so the machine can absorb and discharge sufficient air. Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of cooling pipe.
Super Free Match Service Manual 3.8 Installation of the Outdoor Unit Check the installation location and ensure it is strength and level, so that the unit will not cause any operating vibration or noise after installation. In accordance with the foundation drawing in the following figure, please drill 4 holes in the installation location.
Super Free Match Service Manual 4 INDOOR UNIT INSTALLATION 4.1 Installation of Wall Mounted Type 4.1.1 Important Notices The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself.
Page 77
Super Free Match Service Manual 4.1.5 Installation of Mounting Plate Mounting plate should be installed horizontally. As the water drainage pipe for the indoor unit is two-way type, during installation, the indoor unit should slightly slant to water tray's outlet for smooth drainage of condenser water.
Page 78
Super Free Match Service Manual Put the drain hose into insulating tube. Wrap the insulating tube with wide rubber belt to prevent the shift of insulating tube. Slant the drain hose downward slightly for smooth drainage of condensate. Note: The insulating tube should be connected reliably with the sleeve outside the outlet pipe.
Where there is no corrosive gas, heavy dust, salt mist, smog or moisture. The unit which is installed in the following places is likely to run abnormally. If unavoidable, please contact the professional personnel at the GREE appointed service center: ① Where is full of oil;...
Page 80
Super Free Match Service Manual 4.2.4 Outline Dimension Drawings of the Indoor Unit Note: the unit in the followings figures is mm, unless otherwise specified. Model GFH(09)EA-K3DNA1A/I GFH(12)EA-K3DNA1A/I GFH(18)EA-K3DNA1A/I GFH(21)EA-K3DNA1A/I 1142 1020 1100 1182 GFH(24)EA-K3DNA1A/I 4.2.5 Dimension Requirements on the Installation Space of the Indoor Unit ...
Page 81
Super Free Match Service Manual 4.2.6 Installation of the Indoor Unit Requirements on the Installation Location Ensure the hanger is strong enough to withstand the weight of the unit. The drainage of the drain pipe is easy. No obstacle is in the inlet/outlet and the air circulation is in good condition. Ensure the installation space shown in the following figures is left for the access to maintenance.
Page 82
Super Free Match Service Manual Consult the user and builder for more details. If the strength of the ceiling is not strong enough, a beam made of angle iron can be used and then fix the unit on it. If the indoor unit is not installed in the air conditioning area, please use sponge around the unit to prevent condensing.
Page 83
10 meters far away from the corresponding diffuser. The standard accessories supplied by GREE is the transition duct 200mm long and round air outlet φ200, however, those of other specifications can be purchased.
Page 84
Super Free Match Service Manual Name Name Return Air Louver(with the filter screen) Indoor Unit Canvas Duct Air Supply Duct Return Air Duct Access Grille 4.2.10 Installation of the Condensate Pipe 1) The condensate pipe should keep a inclination angle of 5~10°, which can facilitate the drainage of the condensate water.
Page 85
Super Free Match Service Manual 4.2.12 Installation of the Drain Pipe 1) The diameter of the drain pipe should be larger or equal to that of the refrigerant pipe (PVC pipe, outer dimater:25mm, wall thickness≥1.5mm. 2) The drain pipe should be as short as possible and with at least a 1/100 degree of slope to avoid forming air pockets.
Page 86
Super Free Match Service Manual Notes: ①. The inclination height of the drain hose should be within 75mm so that the outlet of the drain hose does not suffer the external force. ②. If multiple drain pipes converge, please follow the installation steps below. ...
Please contact the local Gree special nominated repair department before installation. Any malfunction caused by the unit that is installed by the department that is not special nominated by Gree would not deal with on time by the inconvenience of the business contact.
Page 88
Super Free Match Service Manual 4.3.3 Outline Dimension Drawings of the Indoor Unit GKH(12)BA-K3DNA2A/I; GKH(18)BA-K3DNA2A/I GKH(12)BA-K3DNA1A/I; GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I INSTALLATION...
Page 89
Super Free Match Service Manual 4.3.4 Installation and Servicing Space The drilling of holes in the ceiling must be done by the professional personnel. 4.3.5 Installation of the Indoor Unit The primary step for install the indoor unit. When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of the hoisting stand to fix it.
Page 90
Super Free Match Service Manual Backout the install cardboard. Note: Please do tighten the nuts and bolts to prevent air conditioner break off. 4.3.6 Drainage hose Install the drain hose The diameter of the drain hose should be equal or bigger than the connection pipe’s. (The diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥...
Page 91
Super Free Match Service Manual Drain stepup pipe note The install height of the drain raising pipe should less than 280mm. The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm.
Page 92
Super Free Match Service Manual Check the smoothness of drain after installation. Check the drain state by immitting 600cc water slowly from the outlet vent or test hole. Check the drain in the state of refrigerating after installation of the electric circuit. ...
Super Free Match Service Manual 4.4 Installation of Floor Ceiling Type 4.4.1 Important Notices T he installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself.
Page 94
Please contact the local Gree special nominated repair department before installation. Any malfunction caused by the unit that is installed by the department that is not special nominated by Gree would not deal with on time by the inconvenience of the business contact.
Page 95
Super Free Match Service Manual Press the fixing knob of the air intake grills, the grilles will be opened wider and then pull them out from the indoor. Remove the side panel fixing screw and pull to the front direction (arrow direction) to remove. Side panel fixing screw.
Page 96
Super Free Match Service Manual INSTALLATION...
Super Free Match Service Manual 4.5 Installation of Console Type 4.5.1 Installation Location and Matters Needing Attention The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit. The user is prohibited from installation by himself.
Page 98
Super Free Match Service Manual 4.5.6 Installation and Servicing Space 4.5.7 Installation of the Indoor Unit Preparation Open the front panel, remove the 4 screws and dismount the front grille while pulling it forward. Follow the arrows to disengage the clasps on the front case to remove Follow the procedure below when removing the slit portions.
Page 99
Super Free Match Service Manual For Side Piping Remove the pillars. ① Remove the 7screws. ② Remove the upper casing (2 tabs). ③ Remove the left and right casings (2 tabs on each side ). ④ Remove the slit portions on the bottom frame and casings using nippers .
Page 100
Super Free Match Service Manual Once refrigerant piping and drain piping connections are complete, fill in the gap of the through hole with putty. A gap can lead to condensation on the refrigerant pipe, and drain pipe, and the entry of insects into the pipes.
Super Free Match Service Manual 5 BU MODULE INSTALLATION 5.1 Precaution for Installation The installation of the air conditioner must be in accordance with the national and local laws and regulations. The quality of the installation will affect the capability of air conditioner directly. The installation should be left to the appointed service center.
Super Free Match Service Manual 5.3 Combinations for Outdoor and Indoor Units Sorts FXA2A-K; FXA2B-K FXA3A-K; FXA3B-K No. of connectable BU modules for each outdoor unit No. of connectable indoor units 5.4 Selection of Installation Location The BU module is for indoor use. BU module must be installed on a firm and solid support which can withstand the weight of the module and the mounting surface must be horizontal plane.
Super Free Match Service Manual 5.5 Outline Dimension and Servicing Space of FXA2A-K Outline dimension Indoor unit side (mm) Sorts Outdoor unit side (mm) Port A Port B Φ6.35 Φ6.35 Φ9.52 Liquid pipe Φ9.52 Φ9.52 Φ15.9 Gas pipe Installation and service space ①...
Super Free Match Service Manual 5.6 Outline Dimension and Servicing Space of FXA2B-K Outline dimension Indoor unit side (mm) Sorts Outdoor unit side (mm) Port A Port B Φ6.2 Φ6.2 Φ9.7 Liquid pipe Φ16.3 Φ16.3 Φ19.3 Gas pipe Installation and service space ①...
Super Free Match Service Manual 5.7 Outline Dimension and Servicing Space of FXA3A-K Outline dimension Indoor unit side (mm) Outdoor unit side Sorts (mm) Port A Port B Port C Φ6.35 Φ6.35 Φ6.35 Φ9.52 Liquid pipe Φ9.52 Φ9.52 Φ9.52 Φ15.9 Gas liquid Installation and service space ①...
Super Free Match Service Manual 5.8 Outline Dimension and Servicing Space of FXA3B-K Outline dimension Indoor unit side (mm) Outdoor unit side Sorts (mm) Port A Port B Port C Φ6.2 Φ6.2 Φ6.2 Φ9.7 Liquid pipe Φ16.3 Φ16.3 Φ16.3 Φ19.3 Gas liquid Installation and service space ①...
Super Free Match Service Manual 5.9 Installation Instruction Check the installation location and ensure it is strength and level. Otherwise, there should be enough space to install drainage pipe, so that the condensed water can be discharged. Reference to the size of hanger metal and drill 4 holes in the installation location. Hang the hanger bolts.
Super Free Match Service Manual 6 REFRIGERATION PIPING WORK 6.1 Manifold Mode of Connecting Pipe For only one BU module, there will not be more than three indoor units. Indoor unit Outdoor uint For two BU modules, there will not be more than six indoor units. For three BU modules, there will not be more than nine indoor units.
Super Free Match Service Manual 6.2 Allowable Length and Drop Height of Connecting Pipe The sorts The pipes Length(m) ≤55 Between outdoor unit and BU L1+L2+L3+L4+L5 ≤60 GWHD(42S)NK3CO Between indoor 1A+1B+1C+2A+2B+2C+ ≤80 Maximum GWHD(48S)NK3CO unit and BU 3A+3B ≤90 allowable GWHD(56S)NK3CO length ≤15...
Super Free Match Service Manual 6.4 Connection of Branch Pipe If two or three BU modules used, Y-type branch pipe of FQ01A/A will be chosen. FQ01A/A (Liquid pipe) FQ01A/A (Gas pipe) Y-type branch pipe is equipped with auxiliary tubes to adjust the diameter of different pipes. If the dimension of the pipe selected is different from the dimension of branch pipe joint, Cut copper tube in the middle with tube cutter and clear up burrs.
Page 111
Super Free Match Service Manual ⑤. See the schematics below: Outdoor unit lower than indoor unit Outdoor unit higher than indoor unit INSTALLATION...
Super Free Match Service Manual 6.6 Connection of Outdoor Unit Refrigerant Pipe ① ② ③ ④ Name Coping plate Rear side plate Front side plate Gas side stop valve ⑤ ⑥ ⑦ Name Liquid side stop valve Right connection board Front connection board Name Front connection...
Page 113
Super Free Match Service Manual Name Port A(mm) Port B(mm) Φ15.9→Φ19.05 Φ15.9 Φ19.05 Φ9.52→Φ12.7 Φ9.52 Φ12.7 Φ9.52→Φ15.9 Φ9.52 Φ15.9 Φ6.35→Φ9.52 Φ6.35 Φ9.52 Install the piping adapter Refer to the piping connection size of the outdoor unit and indoor units, the appropriate piping adapter ①...
Page 114
Super Free Match Service Manual 2) Brazing the piping adapter ① If the connection size of the pipe adapter selected is different from the piping connection size of BU module, cut the tube of the piping adapter from middle with tube cutter and remove the burrs.
Super Free Match Service Manual 6.8 Precaution for Connection Pipe connections should be follow the following rules: ① Outdoor unit shall be installed close to the indoor unit, hence to minimize the length and bends of connection pipes. ② The gap of outdoor unit and indoor units should be as small as possible ③...
Super Free Match Service Manual 6.9 Leak Test Please make sure that the stop valves of the outdoor unit are closed during the operation. The leak test should be made by pressurizing nitrogen gas. Open the pressure reducing valve, pressurize the connection pipes to 1.0 MPa (10 bar) slowly, wait ten minutes, and make sure that the pressure will not drop.
Super Free Match Service Manual 6.11 Refrigerant Charging 6.11.1 The refrigerant has been charged into the outdoor unit before shipped from the manufacturer, while additional refrigerant still need be charged into the refrigerant pipe during the field installation. 6.11.2 Calculation of the Additional Refrigerant Charging 1) Get the refrigerant charge of the outdoor unit from the nameplate.
Page 118
Super Free Match Service Manual The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m). Thus, the total length is over than 30m, so the air conditioner needs to add refrigerant. Additional refrigerant charge Σ Σ the Liquid Pipe Length of Φ6.35×0.022kg/m + the Liquid Pipe Length of Φ9.52×0.054kg/m-1.47(kg) =(5+5+5+5+5+5)(m)×0.022kg/m+(20+10+10)(m)×0.054kg/m-1.47(kg) =1.35(kg)
Page 119
Super Free Match Service Manual c) Turn off the R410A tank and the Hi-knob immediately, when adding refrigerant is enough. Cautio ! ◆ Make sure the liquid and gas side stop valves are opened completely after the installation. ◆ Make sure exact refrigerant charge for the liquid pipe ◆...
Super Free Match Service Manual 7 Electrical Wiring Work 7.1 Wiring Connection The “L”, “3” terminals are connected to the live wire, the “N”,”N(1)” terminals are connected to the neutral wire and the”2” terminal is connected to the transmission line. 7.2 Requirements of Power Circuit and Cable Phase and frequency 1Ph,50Hz...
Super Free Match Service Manual temperature at 40 . If the working condition changes, they should be modified according to the related ℃ national standard. The length of the recommended power cable should be less than 15 meters; otherwise, the diameter of the power cable is not enough.
Super Free Match Service Manual 7.6 Electrical Wiring Work for Outdoor Unit Knock the holes in the plate of the chosen direction with the hammer. Place the rubber ring on the knockout hole. Let the power cable and transmission line go through the knockout hole. Connect the power cable of the outdoor unit to the L, N terminals with the sign of the XT1 and as well as the ground screw.
Page 123
Super Free Match Service Manual b) FXA3A-K and FXA3B-K Terminal black for BU Terminal black for indoor unit power Name Ground screw module power supply supply Name DIP switch Printed circuit board Terminal black for transmission line Let the power cable and transmission line go through the rubber ring. In order to protect the power cable and transmission line from damaging by the hole, the rubber ring cannot fall from that, otherwise, it may cause electrical shock or fire etc.
Super Free Match Service Manual 10) Instructions for DIP Switch 2 digits DIP is adopted to assign the address when using multi-BU modules and the address cannot be repeated in the same unit. One outdoor unit can connect to no more than 3 BU modules. “ON”...
Super Free Match Service Manual 8 INSTALLATION OF DRAINAGE PIPELINE 8.1 Material Quality Requirements for Condensate Pipe Generally, the condensate pipe shall be water supply U-PVC pipe, adhered by using special glue. The other materials available include: PP-R pipe, PP-C pipe and hot-dipped galvanized steel pipe. It is not allowed to use aluminum plastic composite pipe.
Page 126
Super Free Match Service Manual if the drainage is smooth; on another hand, check the piping system for any leakage. Steel sheath shall be provided to the pipe crossing the wall or slab. The pipe joint shall not be positioned within the sheath.
Page 127
Super Free Match Service Manual matter how forcible it pushes, but there is no flowing water, thus resulting in abnormal water level. This will cause flooding of the ceiling. 15) If the air flow of indoor unit is high, this might cause negative pressure and result in return suction of outdoor air.
Page 128
Super Free Match Service Manual NO2: Connection of drain elbow NO3: Connection of horizontal pipe Drainage pipe is requisite for air conditioner unit. During cooling, the moisture in the air will condense on the surface of evaporator. Such condensing water must be drained out of the unit. Meanwhile, the drainage pipe has an important role to determine if the air conditioner can plays its full functions.
Super Free Match Service Manual 9 Installation of Protective Layer on Connection Pipe The refrigerant pipes should be insulated by the insulating material and plastic tape in order to prevent water condensation and leakage. Do not use the foam on the branch pipe as the material for heat insulation. The joints of the system should be wrapped with the insulating material and no gap is allowed on the joint of the system.
Page 130
Super Free Match Service Manual MAINTENANCE MAINTENANCE...
Super Free Match Service Manual MAINTENANCE 1 Testing Board Introduction The testing board is in the front of electrical box and can be observed well. It has several following advantages: Automatically detect indoor unit numbers Automatically assign indoor unit addresses Automatically display real running function and error code Option settings to suit the demand of the customer 1.1 Compose of Testing Board...
Super Free Match Service Manual ① If the malfunction occurs in the outdoor unit, If the malfunction occurs in the system, the the section displays nothing; section will display the error code. If there are Malfunction ② If the malfunction occurs in the indoor units, several malfunctions, it will display the error the section displays the address of the indoor codes by turns...
Page 133
Super Free Match Service Manual ① Long press “Fuc” key for more than 2s to enter the first-level menu. The first-level menu includes control unit and display unit. Press “Enter” key to enter the second-level menu. Press “Fuc” key to switch the menu. Press “Back”...
Super Free Match Service Manual Function Sorts Data section Remarks section Control Unit Blank Use the “+” “-” keys to switch L, N and H. evaporation Default: N If you want to get a higher cooling temperature capacity, select L; else select H. Use the “+”...
Do not repair the air conditioner personally but instead contact the professionally skilled personnel at the GREE appointed service center, as the incorrect repair would cause electric shock or fire hazard etc. 2.1 Check before Contacting Maintenance Serviceman Please check the following items before contacting the maintenance serviceman.
Super Free Match Service Manual Conditions Causes When restart the unit soon after it The overload protection switch of the unit let the The unit does not run is stopped startup delayed for three minutes As soon as power supply is on The unit will stand by for approximate one minute The unit blows out mist When the cooling operation starts...
Page 137
Super Free Match Service Manual Compressor discharge temperature Flash 23 times protection Lack of refrigerant or jam protection Flash 31 times Normal operation Flash 1 time Frequency limitation for current protection Flash 2 times Oil returning mode Flash 3 times Defrosting mode Flash 4 times Frequency limitation for IPM temperature...
Super Free Match Service Manual error Mode conflicts Indoor unit A E6 1A BU 1 Indoor unit B E6 1B Indoor unit C E6 1C Indoor unit A E6 2A Communication BU 2 Indoor unit B E6 2B error Indoor unit C E6 2C Indoor unit A E6 3A...
Super Free Match Service Manual Service personnel shall collect the malfunction information as much as possible and research them thoroughly, list these electrical parts which may cause malfunction, service personnel shall be able to determine the specific reason and solve the faulted parts. Observe the status of the complete device and do not observe the partial.
Page 140
Super Free Match Service Manual Low pressure protection Replace the outdoor unit mainboard Check the Check the pressure with a manometer: low pressure sensor: is Replace the low pressure sensor is it really low? it normal? Check Charge refrigerant according to the amount specified in the refrigerant in the system: is it nameplate and calculated additional amount sufficient?
Super Free Match Service Manual 3.3 Malfunction display: Discharge temperature protection Discharge temperature protection Measure Measure the resistance value of discharge Replace the oudoor discharge temperature: does it have temperature sensor: is it unit mainboard reached 125℃? correct(50KΩ)? Replace relevant discharge temperature sensor Are the Replace relevant electronic...
Super Free Match Service Manual 3.5 Malfunction display: Communication error Communication error Check the Check the orientation of plug cable of indoor unit: is it and socet properly connected? Check the Check the orientation of plug transmission line between outdoor unit and BU module: is it properly and socet connected?
Super Free Match Service Manual 3.6 Malfunction display: Indoor unit water full protection Water full protection Maintain the liquid level switch Check the Replace the mainboard of the Voltage of liquid level Is the water overflow? indoor unit switch : is it ok? Check the Check the Maintain the cables of water...
Super Free Match Service Manual 3.8 Malfunction display: High/Low pressure sensor error Pressure sensor error The plug on pressure sensor is correctly Check the orientation of connected to the socket on plug and socket mainboard, is it? Measure the DC voltage value between black Replace the pressure line and green line of the sensor: is it sensor...
Super Free Match Service Manual 4 POWER DISTRIBUTION 4.1 Diagram of Power Distribution (The thick line represents power line while thin line represents the control line.) MAINTENANCE...
Super Free Match Service Manual 4.2 Wiring diagram Note: This drawing is just for reference; please always refer to the electric wiring stuck to the unit for actual wiring. 4.2.1 Outdoor unit GWHD(56S)NK3CO、GWHD(48S)NK3CO、GWHD(42S)NK3CO MAINTENANCE...
Page 147
Super Free Match Service Manual 4.2.2 Indoor unit Wall mounted type ◆ Hansol GWH(07)TA-K3DNA1E/I; GWH(09)TA-K3DNA1E/I; GWH(12)TB-K3DNA1E/I; GWH(18)TC-K3DNA1E/I ◆ U-Cool GWH(07)UA-K3DNA1B/I; GWH(09)UA-K3DNA1B/I; GWH(12)UB-K3DNA1B/I; GWH(18)UC-K3DNA1B/I MAINTENANCE...
Page 148
Super Free Match Service Manual ◆ Cozy GWH(07)MA-K3DNA3E/I; GWH(09)MA-K3DNA3E/I; GWH(12)MB-K3DNA3E/I;GWH(18)MC-K3DNA3E/I ◆ Change GWH(07)KF-K3DNA6E/I; GWH(09)KF-K3DNA6E/I; GWH(12)KF-K3DNA6E/I; GWH(18)KG-K3DNA6E/I MAINTENANCE...
Page 149
Super Free Match Service Manual ◆ Viola GWH(07)RA-K3DNA3E/I; GWH(09)RA-K3DNA3E/I; GWH(12)RB-K3DNA3E/I; GWH(18)RC-K3DNA3E/I; GWH(24)RC-K3DNA1A/I MAINTENANCE...
Page 150
Super Free Match Service Manual Duct type GFH(09)EA-K3DNA1A/I; GFH(12)EA-K3DNA1A/I; GFH(18)EA-K3DNA1A/I; GFH(21)EA-K3DNA1A/I; GFH(24)EA-K3DNA1A/I Cassette GKH(12)BA-K3DNA2A/I; GKH(18)BA-K3DNA2A/I; MAINTENANCE...
Page 151
Super Free Match Service Manual GKH(12)BA-K3DNA1A/I; GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I Floor ceiling GTH(09)BA-K3DNA1A/I; GTH(12)BA-K3DNA1A/I; GTH(18)BA-K3DNA1A/I; GTH(24)BA-K3DNA1A/I MAINTENANCE...
Page 152
Super Free Match Service Manual Console GEH(09)AA-K3DNA1C/I; GEH(12)AA-K3DNA1C/I; GEH(18)AA-K3DNA1C/I 4.2.3 BU module FXA2A-K; FXA2B-K MAINTENANCE...
Page 153
Super Free Match Service Manual FXA3A-K; FXA3B-K MAINTENANCE...
Super Free Match Service Manual 5 THE RESISTANCES OF COMMON TEMPERATURE SENSORS 5.1 15 KΩ Temp. Resistance Voltage Voltage Temp. Resistance Voltage Voltage (℃) (kΩ) (15K/5V) (15K/3.3V) (℃) (kΩ) (15K/5V) (15K/3.3V) 144.000 0.472 0.311 18.750 2.222 1.467 138.100 0.490 0.323 17.930 2.278 1.503...
Super Free Match Service Manual 6 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 6.1 Outdoor Unit 6.1.1 Disassembly and Assembly of the plates Remarks: Prior to the assembly of the plates, make sure the power supply is cut off. Steps Illustrations Operation Instructions ...
Page 160
Super Free Match Service Manual Unscrew the fixed screws of 4.Disconnect the left left side plate and rear side side plate and rear side plate; plate Remove left side plate and rear side plate. 6.1.2 Assembly and Disassembly of the Compressor Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off.
Page 161
Super Free Match Service Manual 3.Loose the fixed Unscrew the fixed screws of the screw of the compressor compressor base base Remove and replace the compressor. 4.Remove the Note: never let the flame compressor away contact any other from the seating component during the replacement.
Page 162
Super Free Match Service Manual Solder the connecting 6.Solder the pipe to make them pipeline with the connected suction and Note: never let the discharge ports of flame contact any other the compressor component. Tighten the fixing screw of the power cord.
Page 163
Super Free Match Service Manual 6.1.3 Disassembly and Assembly of 4-way valve Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off. Steps Illustrations Operation Instructions a) Unscrew the fixed screws of the magnet 1.Remove the magnet...
Super Free Match Service Manual 6.2 Indoor unit 6.2.1 Wall mounted type ◆ Removal and Assembly of Fan Motor Remark: Prior to the assembly of the motor, make sure the power supply is cut off. Steps Illustrations Operation Instructions Loosen the screws; ...
Page 165
Super Free Match Service Manual 6.2.2 Ducted type ◆ Removal and Assembly of Fan Motor Remark: Prior to the assembly of the motor, make sure the power supply is cut off. Steps Illustrations Operation Instructions Open the cover plate of the 1.Pull out the electric box and then pull electric wire of the...
Page 166
Super Free Match Service Manual Unscrew the fixed screws 5.Loosen the fan of the fan blades and then blade and fan undo the buckle of the motor motor Separate the motor away from the motor support. Remove the fan blade Remove the Take the motor out...
Page 167
Super Free Match Service Manual 6.2.3 One-way cassette type ◆ Assembly and Disassembly of the Water Pump Remark: Prior to the assembly of the drainage pump, make sure the power supply is cut off. Steps Illustrations Operation Instructions Slight press the locks at both ends of the front panel to open one side of it, and then undo Remove the front...
Page 168
Super Free Match Service Manual 6. Unscrew the Unscrew the fixed screws of fixed screws of drainage pump drainage pump 7. Remove drainage Remove drainage pump and pump and replace it replace it 8.Connect the water Connect the water pipe to the pipe to the drainage water pump and then screw pump...
Page 169
Super Free Match Service Manual 6.2.4 Four-way cassette type ◆ Removal and Assembly of Fan Motor Remark: Prior to the assembly of the motor, make sure the power supply is cut off. Steps Illustrations Operation Instructions 1.Unscrew the fixed Unscrew the fixed screws of the water tray screws of the water tray 2.Remove the water tray...
Page 170
Super Free Match Service Manual 4.Remove the fan Remove the fan 5.Loosen the fixed bolts Loosen the fixed bolts of of the fan motor the fan motor 6.Remove the motor and Remove the motor and replace it replace it MAINTENANCE...
Page 171
Super Free Match Service Manual 7.Screw the fixed bolts Screw the fixed bolts of the of the motor motor 8.Mount the fan and Mount the fan and screw screw the fixing bolts the fixing bolts 9.Mount the water tray Mount the water tray and and screw the screws screw the screws...
Page 172
Super Free Match Service Manual ◆ Removal and Assembly of drainage pump Remark: Prior to the assembly of the drainage pump, make sure the power supply is cut off. Steps Illustrations Operation Instructions 1.Unscrew the fixed screws Unscrew the fixed of the water tray screws of the water tray 2.Remove the water tray...
Page 173
Super Free Match Service Manual Connect the drainage Connect the drainage pipe pipe and screw the fixed and screw the fixed screws screws the water pump. the water pump. 6.Mount the water tray and Mount the water tray and tighten the screws tighten the screws MAINTENANCE...
Page 174
Super Free Match Service Manual 6.2.5 Floor ceiling type Remark: Prior to the assembly of the indoor unit, make sure the power supply is cut off. ◆ Removal panel grating module Steps Illustrations Operation Instructions Move down the clip of the ...
Page 175
Super Free Match Service Manual ◆ Remove sub-assy of electric box Steps Illustrations Operation Instructions Remove 3 screws as Remove of electric shown by the arrow in the box cover graph on left and remove the electric box cover. ◆...
Page 176
Super Free Match Service Manual ◆ Remove fixing plate sub-assy for air sweeping fans Steps Illustrations Operation Instructions Remove fixing plate Remove the screws shown sub-assy for air in the graph sweeping fans ◆ Remove fan and motor components Steps Illustrations Operation Instructions...
Super Free Match Service Manual 7.2 Indoor unit 7.2.1 Wall mounted type ◆ Hansol GWH(07)TA-K3DNA1E/I;GWH(09)TA-K3DNA1E/I; GWH(12)TB-K3DNA1E/I; GWH(18)TC-K3DNA1E/I Part list: GWH(07)TA-K3DNA1E/I for CB148N05201; GWH(09)TA-K3DNA1E/I for CB148N05301 GWH(12)TB-K3DNA1E/I for CB148N05401; GWH(18)TC-K3DNA1E/I for CB148N05501 GWH(07)TA-K3DNA1E/I GWH(12)TB-K3DNA1E/ GWH(18)TC-K3DNA1E Description GWH(09)TA-K3DNA1E/I Code Code Code Front Panel 20012853 20012849 20012820U...
Page 181
Super Free Match Service Manual Left Axile Bush 10512037 10512037 1051203701 Propeller Axile Bush 1054202101 1054202101 1054204701 Evaporator Support 24212114 24212114 24212139 Cold Plasma 1114001602 1114001602 1114001601 Generator Evaporator Assy 0100233801 0100294502 0100238601 Cross Flow Fan 10352038 10352033 10352045 Drainage Hose 0523001408 05230014 0523001406...
Page 182
Super Free Match Service Manual ◆ U-Cool GWH(07)UA-K3DNA1B/I; GWH(09)UA-K3DNA1B/I; GWH(12)UB-K3DNA1B/I; Part list: GWH(07)UA-K3DNA1B/I for CB204N02600; GWH(09)UA-K3DNA1B/I for CB204N02700; GWH(12)UB-K3DNA1B/I for CB204N02800 GWH(07)UA-K3DNA1B/I GWH(12)UB-K3DNA1B/I Description GWH(09)UA-K3DNA1B/I Code Code Front Panel Sub-Assy 2001269506 2001285901 Filter Sub-Assy 11122122 11122134 Screw Cover 24252024 24252024 Front Case Sub-assy 20022424 2001272701...
Page 183
Super Free Match Service Manual Axile Bush Sub-assy 10542024 10542024 Evaporator Support 24212132 24212128 Evaporator Assy 0100263001 0100229401 Shield Board (Elbow) 01382010 01382010 Wall Mounting Frame 01252121 01252121 Motor Press Plate 26112270 26112261 Fan Motor 15012125 150120874 Pipe Clamp 26112164 26112164 Rubber Plug (Water Tray) 76712012...
Page 184
Super Free Match Service Manual GWH(18)UC-K3DNA1B/I Part list: GWH(18)UC-K3DNA1B/I for CB204N02900 GWH(18)UC-K3DNA1B/I Description Code Front Panel Assy 2001280401 Filter Sub-Assy 11122133 Screw Cover 24252024 Front Case Sub-assy 2001280503 Guide Louver 2 10512223 Guide Louver 1 10512222 Shaft of guide louver 1054202001 Air Louver(Manual) 10512221...
Page 185
Super Free Match Service Manual Cross Flow Fan 10352030 Evaporator Support 24212135 Evaporator Assy 01002442 Cold Plasma Generator 1114001603 Shield board (elbow) 01382010 Wall Mounting Frame 01252032 Motor Press Plate 26112295 Fan Motor 1501209802 Connecting pipe clamp 26112164 Stepping Motor 15212125 Stepping Motor 15212126...
Page 186
Super Free Match Service Manual ◆ Cozy GWH(07)MA-K3DNA3E/I; GWH(09)MA-K3DNA3E/I; GWH(12)MB-K3DNA3E/I Part list: GWH(07)MA-K3DNA3E/I for CB171N08600; GWH(09)MA-K3DNA3E/I for CB171N08501; GWH(12)MB-K3DNA3E/I for CB171N08701 GWH(07)MA-K3DNA3E/I GWH(12)MB-K3DNA3E/I Description GWH(09)MA-K3DNA3E/I Code Code Receiver Window 20192229 22432230 Front Panel Assy 20012241 20012548 Filter Sub-Assy 11122081 1112220403 Screw Cover 24252016 24252016...
Page 187
Super Free Match Service Manual Rear Case assy 2220210111 2220210301 Rubber Plug (Water Tray) 76712012 76712012 Ring of Bearing 26152022 26152022 O-Gasket sub-assy of Bearing 7651205102 7651205102 Cross Flow Fan 10352018 10352017 Remote Controller 305100491 305100491 Temperature Sensor 390000599 390000599 Ambient Temperature Sensor 390000453 '390000453...
Page 188
Super Free Match Service Manual GWH(18)MC-K3DNA3E/I Part list: GWH(18)MC-K3DNA3E/I for CB171N08401 GWH(18)MC-K3DNA3E/I Description Code Receiver Window 22432173 Front Panel Assy 20012260 Filter Sub-Assy 1112208901 Screw Cover 24252016 Baffle Plate 26112228 Front Case Sub-Assy 20022172 Air Louver 2 10512117 Air Louver 1 10512116 Helicoid tongue 26112238...
Page 189
Super Free Match Service Manual Ring of Bearing 26152022 O-Gasket sub-assy of Bearing 7651205102 Cross Flow Fan 10352019 Remote Controller 305100491 Temperature Sensor 390000599 Ambient Temperature Sensor 390000453 Connecting Cable 4002052317 Evaporator Support 24212133 Evaporator Assy 01002774 Wall Mounting Frame 01252218 Motor Press Plate 26112494...
Page 190
Super Free Match Service Manual ◆ Change GWH(07)KF-K3DNA6E/I;GWH(09)KF-K3DNA6E/I;GWH(12)KF-K3DNA6E/I; WH(18)KG-K3DNA6E/I Part list: GWH(07)KF-K3DNA6E/I for CB146N26201; GWH(09)KF-K3DNA6E/I for CB146N26301; GWH(12)KF-K3DNA6E/I for CB146N26401; GWH(18)KG-K3DNA6E/I for CB146N26501 GWH(07)KF-K3DNA 6E/I GWH(12)KF-K3DNA6 GWH(18)KG-K3DN Description GWH(09)KF-K3DNA A6E/I 6E/I Code Code Code Membrane 63062017 63062017 63062022 Front Panel Assy 20012443S 20012443S 20012495S...
Page 191
Super Free Match Service Manual Guide Louver 10512119 10512119 10512140 Shaft of guide louver 1054202001 1054202001 10512037 Air Louver 10512160 10512160 10512160 Helicoid tongue 26112486 26112486 26112232 Rear Case assy 2220229501 2220229501 22202154 Pipe plug (outlet) 76712020 76712020 76712012 Axile Bush sub-assy 10542024 10542024 10542047...
Page 192
Super Free Match Service Manual ◆ Viola GWH(07)RA-K3DNA3E/I;GWH(09)RA-K3DNA3E/I;GWH(12)RB-K3DNA3E/I;GWH(18)RC-K3DNA3E/I Part list: GWH(07)RA-K3DNA3E/I for CB302N01501; GWH(09)RA-K3DNA3E/I for CB302N01601; GWH(12)RB-K3DNA3E/I for CB302N01701; GWH(18)RC-K3DNA3E/I for CB302N01801 GWH(07)RA-K3DNA3E/I GWH(12)RB-K3DNA3E/I GWH(18)RC-K3DNA3E/I Description GWH(09)RA-K3DNA3E/I Code Code Code Front Panel Assy 20012878 20012858 20012760 Display Board 30565137 30565137 30565121 Filter Sub-Assy 11122206...
Page 193
Super Free Match Service Manual Guide Louver 10512204 10512203 10512205 Air Louver 1 1051211302 1051215603 1051211602 Air Louver 2 1051211402 1051215503 1051211702 Helicoid Tongue 2611216202 2611216302 2611223802 Axile Bush 10542036 10542036 10542036 Rear Case assy 22202186 22202467 22202193 Cross Flow Fan 10352018 10352017 10352019...
Page 194
Super Free Match Service Manual GWH(24)RC-K3DNA1A/I Part list: GWH(24)RC-K3DNA1A/I for CB144N01100 GWH(24)RC-K3DNA1A/I Description Code Front Panel Assy 20012734 Filter Sub-Assy 11122091 Screw Cover 24252016 Front Case 2001297002 Air Louver 1 1051215901 Helicoid Tongue 2611218702 Left Axile Bush 10512037 Rear Case assy 22202363 Rubber Plug (Water Tray) 76712012...
Page 195
Super Free Match Service Manual Evaporator Assy 01002437 Wall Mounting Frame 01252032 Motor Press Plate 26112316 Fan Motor 15012098 Pipe Clamp 2611218801 Drainage hose 0523001405 Step Motor 1521300101 Crank 10582070 Display Board 30565110 Guide Louver 10512208 Axile Bush 10542036 Electric Box 20112108 Terminal Board 42011233...
Page 196
Super Free Match Service Manual 7.2.2 Duct type GFH(09)EA-K3DNA1A/I; GFH(12)EA-K3DNA1A/I Part list: GFH(09)EA-K3DNA1A/I for CN210N0010; GFH(12)EA-K3DNA1A/I for CN210N0020 GFH(09)EA-K3DNA1A/I GFH(12)EA-K3DNA1A/I Description Code Code Air outlet frame assy 01865216 01865216 Cover of air outlet 01265298 01265298 Water Tray Assy 01285332 01285332 Top Cover Board Assy 01265200099 01265325...
Page 197
Super Free Match Service Manual Terminal Board 420111041 420111041 Main Board 30226338 30226338 Capacitor 33010020 33010027 Electric Box Sub-Assy 01395100 01395100 Electric Box assy 01395980 01395983 Electric Box Cover 01424253 01424253 Cover Plate of the Fan 01265300 01265300 Bottom Cover Plate 01265299 01265299 Supporter...
Page 198
Super Free Match Service Manual GFH(18)EA-K3DNA1A/I Part list: GFH(18)EA-K3DNA1A/I for CN210N0030; GFH(18)EA-K3DNA1A/I Description Code Air outlet frame assy 01865217 Cover of air outlet 01265331 Water Tray Assy 01285333 Evaporator Assy 01024268 Lower Cover Plate Sub-Assy 01265328 Left Side Plate Assy 01315334 Plate of the Evaporator Sub-Assy 01495317...
Page 199
Super Free Match Service Manual Rear volute casing 26905206 Bottom Cover Plate 01265332 Transformer 43110233 Terminal Board 420111041 Main Board 30226338 Capacitor 33010027 Electric Box Sub-Assy 01395100 Electric Box assy 01395984 Electric Box Cover 01424253 Temperature Sensor 390001982G Ambient Temperature Sensor 39000206 Cover Plate of the Fan 01265333...
Page 200
Super Free Match Service Manual GFH(21)EA-K3DNA1A/I; GFH(24)EA-K3DNA1A/I Part list: GFH(21)EA-K3DNA1A/I for CN210N0040; GFH(24)EA-K3DNA1A/I for CN210N0050 GFH(21)EA-K3DNA1A/I Description GFH(24)EA-K3DNA1A/I Code Air outlet frame assy 01375224 Cover of air outlet 01265335 Water Tray Assy 01285334 Evaporator Assy 01024269 Lower Cover Plate Sub-Assy 01265339 Left Side Plate Assy '01315334...
Page 201
Super Free Match Service Manual Front volute casing 26905205 Rear volute casing 26905206 Bottom Cover Plate 01265337 Transformer 43110233 Terminal Board 420111041 Main Board 30226338 Capacitor 33010027 Electric Box Sub-Assy 01395100 Electric Box assy 01395985 Electric Box Cover 01424253 Cover Plate of the Fan 01265338 Temperature Sensor 390001982G...
Page 202
Super Free Match Service Manual 7.2.3 Cassette type GKH(12)BA-K3DNA2A/I; GKH(18)BA-K3DNA2A/I MAINTENANCE...
Page 203
Super Free Match Service Manual Part list: GKH(12)BA-K3DNA2A/I for CN510N0040; GKH(18)BA-K3DNA2A/I for CN510N0050 GKH(12)BA-K3DNA2A/I(Body ) GKH(18)BA-K3DNA2A/I(Body) Description Code Code Seat Board Sub-Assy 01222712 01222712 Front Side Plate 01302741 01302741 Right Baffle Assy 01362704 01362704 Water Pump 43130320 43130320 Pump Drainpipe 05232722 05232722 Body Installing Support...
Page 204
Super Free Match Service Manual GKH(12)BA-K3DNA1A/I; GKH(18)BA-K3DNA1A/I; GKH(24)BA-K3DNA1A/I Part list: GKH(12)BA-K3DNA1A/I for CN510N0010;GKH(18)BA-K3DNA1A/I for CN510N0020; GKH(24)BA-K3DNA1A/I for CN510N0030 MAINTENANCE...
Page 205
Super Free Match Service Manual GKH(12)BA-K3 GKH(18)BA-K3 GKH(24)BA-K3 Description DNA1A/I DNA1A/I DNA1A/I Code Code Code Tube Exit Plate Assy 01382717 01382717 01382715 Shell Assy 01432701 01432701 01432704 Body Installing Plate 01332701 01332701 01332701 Front Side Plate Assy 01302717 01302717 01302718 Left Side Plate Assy 01302740 01302740...
Page 206
Super Free Match Service Manual 7.2.4 Floor ceiling type GTH(09)BA-K3DNA1A/I; GTH(12)BA-K3DNA1A/I Part list: GTH(09)BA-K3DNA1A/I for CN610N0010; GTH(12)BA-K3DNA1A/I for CN610N0020 GTH(09)BA-K3DNA1A/I GTH(12)BA-K3DNA1A/I Description Code Code Fixed Mount 26909426R 26909426R Louver Clamp 26112127 26112127 Guide Louver 10619403 10619403 Rotating Shaft 26909430 26909430 Front Connecting Plate 01349414P 01349414P...
Page 207
Super Free Match Service Manual Air Lead Plate sub-assy 02229418 02229418 Supporter 01805288 01805288 Mid-clapboard sub-assy 01249416 01249416 Front volute casing 26905205 26905205 Rear side plate assy 01319430 01319430 Centrifugal fan 10425200 10425200 Support 1 01809417 01809417 Right Side Plate Sub-Assy 01319429 01319429 Right Cover Plate...
Page 208
Super Free Match Service Manual GTH(18)BA-K3DNA1A/I Part list: GTH(18)BA-K3DNA1A/I for CN610N0030; GTH(18)BA-K3DNA1A/I Description Code Fixed Mount 26909426R Louver Clamp 26112127 Guide Louver 10619403 Rotating Shaft 26909430 Front Connecting Plate 01349414P Air Louver 10619404 Base Frame 26909448 MAINTENANCE...
Page 209
Super Free Match Service Manual Air Lead Plate sub-assy 02229418 Supporter 01805288 Mid-clapboard sub-assy 01249416 Front volute casing 26905205 Rear side plate assy 01319430 Centrifugal fan 10425200 Support 1 01809417 Axile Bush 10542704 Right Side Plate Sub-Assy 01319429 Right Cover Plate 26909444 Installation Supporting Frame 01809402...
Page 210
Super Free Match Service Manual GTH(24)BA-K3DNA1A/I Part list: GTH(24)BA-K3DNA1A/I for CN610N0040; GTH(24)BA-K3DNA1A/I Description Code Cable-Cross Loop 76510021 Room Sensor 39000191 Louver Clamp 26112127 Guide Louver 10619403 Front Connecting Plate 01349414P Rotating Shaft 26909430 Air Louver 10619404 Base Frame 26909448 MAINTENANCE...
Page 211
Super Free Match Service Manual Induced air plate subassembly 02229418 Supporter 01805288 Mid-clapboard sub-assy 01249416 Front volute casing 26905205 Rear side plate assy 01319430 Centrifugal fan 10425200 Supporter 01809417 Support Of Motor Bearing 01792408 Axile Bush 10542704 Right Side Plate Sub-Assy 01319429 Right Cover Plate 26909444...
Page 212
Super Free Match Service Manual 7.2.5 Console type GEH(09)AA-K3DNA1C/I; GEH(12)AA-K3DNA1C/I; GEH(18)AA-K3DNA1C/I MAINTENANCE...
Page 213
Super Free Match Service Manual Part list: GEH(09)AA-K3DNA1C/I for CV010N01500; GEH(12)AA-K3DNA1C/I for CV010N01600; GEH(18)AA-K3DNA1C/I for CV010N01700 GEH(09)AA-K3 GEH(12)AA-K3 GEH(18)AA-K3 Description DNA1B/I DNA1B/I DNA1B/I Code Code Code Front Panel Assy 20012756 20012756 20012756 Filter Sub-Assy 11122139 11122139 11122139 Front Case Assy 20012601 20012601 20012601...
Need help?
Do you have a question about the GC201306 -1 and is the answer not in the manual?
Questions and answers