Electrical Wiring Work; Wiring Connection; Requirements Of Power Circuit And Cable - Gree GC201306 -1 Service Manual

Super free match series, t1/r410a/50hz
Table of Contents

Advertisement

Super Free Match
Service Manual

7 Electrical Wiring Work

7.1 Wiring Connection

The "L", "3" terminals are connected to the live wire, the "N","N(1)" terminals are connected to the neutral
wire and the"2" terminal is connected to the transmission line.

7.2 Requirements of Power Circuit and Cable

Recommended cable of outdoor unit
(Pieces × Sectional area)
Recommended cable of BU module (Pieces × Sectional area)
Recommended cable of indoor unit (Pieces × Sectional area)
Capacity of the air switch
Note:
The total length of the transmission line between the outdoor unit and the furthest BU module is not more
than 55m. Otherwise, the system cannot work possibility.
The specifications of the power cable and transmission line listed in the table above are determined based
on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-guarded
multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and a PVC cable jacket)
used at 40
(code designation 60245 IEC 57). If the working condition changes, they should be modified according to
the related national standard.
The specifications of the air switch listed in the table above are applied to the breaker with the working
INSTALLATION
116
Phase and frequency
Voltage
Transmission line (Pieces × Sectional area)
and resistible to 90
℃, and shall be at least those of ordinary polychloroprene sheathed cords
GWHD(42S)NK3CO
GWHD(48S)NK3CO
GWHD(56S)NK3CO
GWHD(42S)NK3CO
GWHD(48S)NK3CO
GWHD(56S)NK3CO
BU module
1Ph,50Hz
220~240V
2
3×6.0 mm
2
3×0.75 mm
2
2×1.5 mm
2
4×0.75mm
32A
40A
40A
10A