Vent Termination Clearances (Vertical Cap Requirements) - kozy heat Lakefield 56150 Installation Manual

Free-standing direct vent gas fireplace
Table of Contents

Advertisement

VENT TERMINATION CLEARANCES
Roof Pitch
Flat to 6/12
Over 6/12 to 7/12
Over 7/12 to 8/12
Over 8/12 to 9/12
Over 9/12 to 10/12
Over 10/12 to 11/12
Over 11/12 to 12/12
Over 12/12 to 14/12
Over 14/12 to 16/12
Over 16/12 to 18/12
Over 18/12 to 20/12
Over 20/12 to 21/12
CAUTION
This appliance must not be connected to or joined with any chimney flue serving any other appliance.
Approved Cap
Discharge opening
Approved vent pipe
Figure 12a
VENTING
H (Min.) Ft.
H (Min.) m
1.0
0.30
1.25
0.38
1.5
0.46
2.0
0.61
2.5
0.76
3.25
0.99
4.0
1.22
5.0
1.52
6.0
1.83
7.0
2.13
7.5
2.27
8.0
2.44
(Vertical Cap Requirements)
Minimum
*8ft. (2.44m)
H
X
12
H - Minimum height from roof to lowest discharge opening
* If vent is closer than 8ft. (2.44m), it must terminate at least
2ft. (0.61m) higher than any portion of a building within 10ft.
(3.05m) of the vent.
12
Roof pitch = X/12