DETERMINE INSTALLATION HEIGHT

This hood can be installed for vented or recirculating
operation. All necessary parts are shipped with the hood
for recirculation mode.
NOTE: Installation height should be measured from
the cooking surface to the bottom of the hood.
The vent hood must be installed 24" min. and
36" max. above the cooking surface.
24" Min.
36" Max.
Recirculation Mode
You must use the riser with louvers facing the front
side with recirculation mode. The hood height with
the riser is 14". Do not knock out the duct opening
on the riser.
DO NOT knock out
the duct opening for
recirculation mode.
Installation Preparation
Riser
8
To determine the distance between the bottom of
the hood and the cooking surface (Min 24", Max. 36"
use the following formula to solve for X:
X = C - (A + B + R + Y + Z) where
A = Cooking surface to the floor
B = Hood height without riser
C = Ceiling height
R = Riser height (must be used with recirculation
mode, optional for vent mode)
Y = Cabinet height
Z = Soffit/Gap between the cabinet and ceiling (may
be "0")
Example: X = 96" - (36" + 10 1/2" + 3 1/2" + 15" + 6")
X = 25"
Z
Y
R=3 1/2"
B=10 1/2"
C=Ceiling
Height
X=24" Min, 36" Max
A