McQuay MDS030AR Applications Manual page 89

Multi-digital scroll units
Hide thumbs Also See for MDS030AR:
Table of Contents

Advertisement

E
A
o
s
B
C
D
Ball valve (liquid side)
M
K
Ball valve (gas side)
cap. The moment to tighten the access opening cap is 12 N m to 15 N m.
H Flare fitting
For the tightening moment, refer to the figure in next page. Loosen and screw up the screw with a double-end
wrench. Coat refrigerant oil on the contact surface of the flare fitting (Type R22 mineral oil is applicable).
K Field connection pipe
Braze to the connection pipe. (Please use non-oxidative brazing materials)
The following table shows the dimension of the copper flare fitting.
Outer diameter
Metric system
British measurement
6.35
1/4
9.52
3/8
12.7
1/2
15.88
5/8
19.05
3/4
The following table shows the dimension of the nut of the flare fitting nut.
Outer diameter
Metric system
British measurement
6.35
1/4
9.52
3/8
12.7
1/2
15.88
5/8
19.05
3/4
When connecting the liquid pipe and liquid stop valve, align the center of the flare fitting of the liquid pipe
to that of the stop valve, and then tighten with a moment wrench. Whether tightened with the wrench
depends on the setting of the wrench range and the tightening angle. The following table shows the
external pipe diameter, the corresponding tightening moment and the tightening angle.
Outer diameter (mm) Tightening moment (N . m) Tightening angle(
6.35
9.52
12.7
15.88
19.05
A Valve handle
(Before pipe connection, vacuum pumping and additional refriger-
E
ant filling for delivery, make sure this valve is closed completely.
After the above operations, please fully open it.)
F
B Stop pin (prevent the valve handle from turning over 90 degrees)
C Sealing plate (annex)
o
s
D Connection pipe (annex)
G
Install the pipe firmly to the valve flange with the sealing plate to
avoid gas leakage.
E Open (slow operation)
F Cap and copper spacer
L
H
Remove the cap and operate the handle. After the operation,
reinstall the cap. The moment to tighten the valve handle cap is 23
Nm to 72 Nm.
G Access opening
Pump vacuum for the refrigerant pipe through this access opening,
and fill additional refrigerant on the site. Open and close the access
opening with a double-end wrench. After the operation, reinstall the
Outer diameter
9.0
13.0
16.2
19.4
23.3
Outer diameter
17.0
22.0
24.0
27.0
36.0
14 18
60 90
35 42
60 90
50 57.5
30 60
75 80
30 60
100 140
20 35
Design & installation Guide For McQuay MDS Multi System
o
)
Unit: mm
Unit: mm
Outer diameter size
-89-