Specifications Recognize this symbol as an indication of Important Safety Information! General The Combination Gas Heating/Electric Cooling Rooftop is available in 100,000 & 135,000 BTU/Hr. heating inputs and Introduction cooling capacities of 6 nominal tons of cooling. Units are convertible from bottom supply and return to side supply and ▲...
Safety Information ▲ ▲ ▲ ▲ WARNING WARNING Use only with type of gas approved for this unit. Refer to the When a unit is installed so that supply ducts carry air unit rating plate. circulated by the unit to areas outside the space containing the unit, the return air shall also be handled by duct(s) sealed to the unit casing and terminating outside the space ▲...
Unit Dimensions For clearances see page 9, Fgure 7. IMPORTANT: This unit must be mounted level in both directions to allow water to drain from the condenser section and condensate pan. Figure 1: Bottom View BASE ELECTRICAL BASE GAS ENTRY ENTRY CONDENSER COIL...
Page 6
Figure 3: Cabinet Dimensions and Access Locations 46.5 81.53 FLUE OUTLET SUPPLY GAS ENTRY 1/2” NPT 7.22 COMBUSTION AIR INLET 30.25 POWER ENTRY BURNER ACCESS CONTROL ENTRY 12.69 COMPRESSOR/ CONTROL BOX 17.75 14.63 ACCESS ST-A0801-16 Figure 4: Supply and Return Dimensions for Horizontal Applications – Back View RETURN SUPPLY 12.25...
Installation 2 Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection. General 3 A good liquid cleaner may be used several times a year to 1 INSTALLATION — Install this unit in accordance with remove matter that will not wash off with water.
Figure 6: Cover gasket detail for units shipped for 4 Locate unit where operating sounds will not disturb downflow application being converted to horizontal. owner or neighbors. 5 Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
Figure 8: Flat rooftop installation, attic or drop ceiling On ductwork exposed to outside temperature and humidity, distributing system. Mounted on roofcurb. Curb must be use a minimum of 2 of insulation and a vapor barrier. level. Distribution system in attic, furred space or crawl space should be insulated with at least 2 of insulation.
Figure 10: Roofcurb Figure 11: Roofcurb UNIT ROOFTOP UNIT NOTE: Remove shipping boards 1/4 TYP (3) SIDES from unit before *SEE NOTE installing on the roofcurb. GASKET COUNTER FLASHING* HOLD DOWN NAILER STRIP BRACKET TYP. (4) LCS. INSULATION* DUCT* GASKET (FULL PERIMETER CANT STRIP* AND ON DIVIDERS.
IMPORTANT: Check the rating plate to make certain the unit is Table 3: LP Gas Pipe Capacity Table (Cu. Ft./Hr.) equipped to burn the type of gas supplied. Care should be taken after installation of this equipment that the gas control valve not Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water column inlet pressure).
Figure 13: LP Conversion Kit Figure 14 MANIFOLD PIPE Figure 15: Condensate Drain IMPORTANT NOTE FOR ALTITUDES ABOVE 2,000 FEET (610 METERS): The main burner orifices in your furnace and in these kits are sized for the nameplate input and intended for installations at elevations up to 2,000 feet in the USA or Canada, or for elevations of 2,000 - 4,500 feet (610 -1,373 meters) in Canada if the unit has been derated at the factory.
Figure 16: Recommended Branch Circuit Disconnect ampacity found on the unit rating plate. Use the smallest Location wire size allowable in Table 5 from the unit disconnect to unit. NOTE: A bracket is provided with the unit for mounting the branch circuit disconnect to the unit.
To Start The Furnace 8 Thermostat is satisfied and opens. 1. STOP! Read the safety information on the Operating 9 The gas valve is de-energized and closes, shutting down the Instructions Label located on this unit. burner flame. ▲ ▲ 10 The control board will de-energize the inducer after a five DANGER second post purge.
▲ ▲ System Operating Information DANGER Advise The Customer Should overheating occur or the gas supply fail to shut off, shut off the manual gas valve to the unit before shutting off 1 Change the air filters regularly. The heating system the electrical supply.
Cooling Section 9 Remove the screws (3) connecting the divider plate to the heat exchanger center panel. Maintenance 10 Remove the turbulators from inside the heat exchangers by ▲ ▲ inserting the blade of a screwdriver under the locking tabs. DANGER Pop the tabs out of the expanded grooves of the heat exchanger.
3 The coil should be cleaned when it is dry. If the coil is coated with dirt or lint, vacuum it with a soft brush To find your local McQuay Certified Parts Distributor, go to attachment. Be careful not to bend the coil fins.
Page 23
General Data Nominal Sizes 6 Tons [21.1 kW] ASHRAE 90.1-2004 Compliant Models Model MPS- 006AGYL13E 006AGYM13E Cooling Performance Gross Cooling Capacity Btu [kW] 75,000 [22] 75,000 [22] EER/SEER 10.3/NA 10.3/NA Nominal CFM/ARI Rated CFM [L/s] 2400/2400 [1133/1133] 2400/2400 [1133/1133] ARI Net Cooling Capacity Btu [kW] 72,000 [21.1] 72,000 [21.1] Net Sensible Capacity Btu [kW]...
Page 24
Miscellaneous ELECTRICAL DATA Model MPS- 006AGCL10E 006AGCL13E 006AGCM10E 006AGCM13E 006AGDL10E 006AGDL13E 006AGDM10E 006AGDM13E Unit Operating 187-253 187-253 187-253 187-253 414-506 414-506 414-506 414-506 Voltage Range Minimum Circuit Ampacity 34/34 34/34 34/34 34/34 Minimum Overcurrent 40/40 40/40 40/40 40/40 Protection Device Size Maximum Overcurrent 40/40 40/40...
Page 25
Figure 19: Cooling Trouble Shooting Chart ▲ ▲ DANGER Disconnect all power to unit before servicing. Contactor may break only one side. Failure to shut off power can cause electrical shock resulting in personal injury or death. SYMPTOM POSSIBLE CAUSE REMEDY Unit will not run •...
Page 26
Figure 20: Furnace Troubleshooting Guide (Combination Heating and Cooling Units With Direct Spark Ignition) WARNING HAZARDOUS VOLTAGE DISCONNECT POWER BEFORE LINE VOLTAGE SERVICING. CONNECTIONS SERVICE MUST BE BY A TRAINED, QUALIFIED SERVICE TECHNICIAN. START SET THERMOSTAT TO CALL FOR HEAT SET FAN SWITCH TO AUTO •...
Page 27
NOTE: IF THE SYSTEM GOES INTO LOCKOUT, WAIT 30 SECONDS AND RESET THE SYSTEM. REPLACE SENSOR MAIN BURNER FLAME SUSTAINED • CHECK FLAME SENSOR POSITION AND CONDITION • CLEAN FLAME SENSOR WITH STEEL WOOL • CHECK FLAME SENSOR WIRES AND CONNECTIONS REPLACE IGNITION CONTROL •...
Page 30
Figure 23: System Charge Charts 6 TON COOLING - CIRCUIT 1 SYSTEM CHARGE CHART – REFRIGERANT 22 6 TON, CIRCUIT 1 IM 861...
Page 31
Figure 24: System Charge Charts 6 TON COOLING - CIRCUIT 2 SYSTEM CHARGE CHART – REFRIGERANT 22 6 TON, CIRCUIT 2 IM 861...
Page 32
McQuay Training and Development Now that you have made an investment in modern, efficient McQuay equipment, its care should be a high priority. For training information on all McQuay HVAC products, please visit us at www.mcquay.com and click on training, or call 540-248-9646 and ask for the Training Department.
Need help?
Do you have a question about the Maverick I MPS006AG Series and is the answer not in the manual?
Questions and answers