4.1 Outdoor Unit Installation

To choose location of installation
To ensure good cooling and heating performance of the units, follow up the below to pick up right
place to install units:
To avoid discharged air returns to the air inlet, to avoid hot air discharged by other units;
ensure enough space for maintenance.
To remove any barrier of air ventilation both air supply and air discharge.
Maintain good ventilation for better heat exchange efficiency.
Installation base shall be strong enough to support the units and prevent vibration.
To avoid installing units at dirty and salty place.
Do not install units at easy burning gas leakage place. Accumulated burning gas leakage
may result in an explosion.
Do not install units to the place where the units are inclined to be damaged by typhoon and
strong wind. If possible, install rainproof, snow-shield, and lightproof equipment.
Space for installation of outdoor units
One single outdoor unit can be installed in one place, multiple outdoors can be installed in one
big place in order. For details, see the following:
Space for single outdoor unit
BACK
FRONT
45¡ª
FRONT
Space for more than one units
BACK
FRONT
Design & installation Guide For McQuay MDS Multi System
450mm
450mm
AIR OUTLET GUIDE
1000mm
BACK
FRONT
450mm+h1
450mm+h3
FR ONT
450mm
900mm
900mm
FRONT
FRONT
FRONT
450mm+h2
100mm+h4
450mm