McQuay MDS030AR Applications Manual page 38

Multi-digital scroll units
Hide thumbs Also See for MDS030AR:
Table of Contents

Advertisement

Design & installation Guide For McQuay MDS Multi System
220V~/50Hz
PTC
PTC
-38-
2.6.2 Wiring Diagram of Outdoor Units
Model MDS030A
L
FU
1L1
3L2
5L3
KM
2T1
4T2
6T3
blue
red
C
Shaft
white
heater
R
CM
C2
13
C1
S
14
black
white
Compressor
Description of components and parts:
Description
Symbol
Description
Symbol
Fuse
FU
PTC
Compressor start-up unit
KM
Contactor
EXV
Electric expansion valve
Solenoid valve
Capacitor
PWMV
C1-3
HP
High pressure switch
LP
Low pressure switch
Model MDS030AR
220V~/50Hz
L
FU
1L1
3L2
5L3
KM
2T1
4T2
6T3
blue
red
C
white
Shaft
heater
R
CM
13
C1
S
14
white
Compressor
black
Description of components and parts:
Symbol
Description
Symbol
Description
PTC
Compressor start-up unit
FU
Fuse
4WV
Four-way valve
EXV
Electric expansion valve
KM
Contactor
PWMV
Solenoid valve
C1-2
Capacitor
LP
Low pressure switch
HP
High pressure switch
RC
Surge suppressor
2
NEUTRAL
N
Trans-
former
M
~
Fan 1
Jumper settings
DIP switch J2 setting:
JP1
JP2
J2.6
OFF
OFF
ON
Notes:
DIP switch J1 settings:
1: -----------Field wiring
J1.1
J1.2 J1.3
J1.4 J1.5 J1.6 J1.7
2: --------------
Factory wiring
3: J2.1~2.5 sets the internetworking control address
OFF OFF OFF OFF OFF OFF ON
4: If the unit connected at the end of the bus,JP1,JP2 is on.
2
N
Trans-
former
C2
M
~
Fan 1
Jumper settings
DIP switch J2 setting:
JP1
JP2
J2.6
OFF
OFF
OFF
DIP switch J1 settings:
J1.1
J1.2
J1.3
J1.4
J1.5
J1.6
J1.7
OFF
OFF
OFF
OFF
ON
OFF
ON
EXV
PWMV
KM
5
3
7
LIVE
RY1
RY2
RY3
RY4
RY5
J2
TRAN-H
McQuay
CN1
TRAN-L
J1
JP1
JP2
A
B
GND
AI-IN
Connecting indoor
unit communication
Air discharge temperature sensor of the digital compressor(TH1)
RC
EXV
PWMV
4WV
KM
5
3
4
7
LIVE
RY1
RY2
RY3
RY4
RY5
NEUTRAL
J2
TRAN-H
CN1
McQuay
TRAN-L
J1
JP1
JP2
A
B GND
AI-IN
Connecting indoor
unit communication
Air discharge temperature sensor of the digital compressor(TH1)
Notes:
1: -----------Field wiring
Factory wiring
2: --------------
3: J2.1~2.5 sets the internetworking control address
4: If the unit connected at the end of the bus,JP1,JP2 is on.
8
10
RY6
RY7
NEUTRAL
OV-COMP3
OV-COMP2
OV-COMP1
LP
11
LP
HP
HP
12
Coil middle
temperature sensor(TH5)
Return air temperature sensor(TH3)
Ambient temperature sensor(TH2)
8
10
RY6
RY7
NEUTRAL
OV-COMP3
OV-COMP2
OV-COMP1
LP
LP
11
HP
HP
12
Coil outlet
temperature sensor(TH6)
Coil middle temperature sensor(TH5)
Coil inlet temperature sensor(TH4)
Return air temperature sensor(TH3)
Ambient temperature sensor(TH2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents