10.2.1
Measurement checking sensors during fault tracing
Table 8.
Outdoor sensor / Defrost sensor
°C
ohm, Ω
-30
1884
-25
1443
-20
1115
-15
868
-10
681
-5
538
0
428
5
343
10
276
15
224
20
183
25
150
30
124
35
103
40
86
10.3

Check points

Table 10.
Temperatures
Name
Condensing temperature
Evaporation temperature
Superheating
Radiator circuit
Brine circuit
Overheating R407C
Table 11.
Expansion valve factory setting
Name
Danfoss TUBE R404A, 4.2 kW
Danfoss TUBE R404A, 5.6 kW
Danfoss TUBE R404A, 8,4 kW
Danfoss TUBE R404A, 12.0 kW
Danfoss TUBE R404A, 15.3 kW
36 – Service instructions VMGFC302
Values
0.5 – 1.5 °C above supply line temperature
7 - 8 °C lower than incoming brine
4 - 8 K temperature difference
5 - 10 K temperature difference
2 - 5 K temperature difference
4K ±1 K
Setting
From fully closed position, screw 3 turns out
From fully closed position, screw 5,5 turns out
From fully closed position, screw 5 turns out
From fully closed position, screw 5.25 turns out
From fully closed position, screw 2.75 turns out
Table 9.
other sensors
°C
kilo ohm, kΩ
0
66,3
5
52,4
10
41,8
15
33,5
20
27,1
25
22,0
30
18,0
35
14,8
40
12,2
45
10,1
50
8,5
55
7,1
60
6,0
65
5,0
70
4,2
75
3,7
80
3,1
85
2,7