Measurement Points; Check Points - Danfoss DHP-AX Installation And Service Instructions Manual

Hide thumbs Also See for DHP-AX:
Table of Contents

Advertisement

15.2

Measurement points

Conversion table for sensors
D B
BB
When reading the resistance of the sensors, the sensor leads must first be disconnected from the control
equipment.
Outdoor sensor
°C
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
15.3

Check points

Temperatures
Name
Condensing temperature
Evaporation temperature
Overheating
Radiator circuit
Overheating R407C
Other sensors
°C
Ohm, Ù
1884
0
1443
5
1115
10
868
15
681
20
538
25
428
30
343
35
276
40
224
45
183
50
150
55
124
60
103
65
86
70
75
80
85
90
95
1.
Kiloohm,
2.
66,3
52,4
3.
41,8
33,5
27,1
22,0
18,0
14,8
12,2
10,1
8,5
7,1
6,0
5,0
4,2
3,7
3,1
2,7
2,3
2,0
Values
0.5 – 1.5 °C above supply line temperature
7 - 8 °C lower than incoming brine
4 - 8 K temperature difference
5 - 10 K temperature difference
4K ±1 K
VMBMH302
Disconnect the sensor cable at the I/O
card.
First measure the sensor including the
cable.
Then measure the sensor only.
Service – 45