Check Points - Danfoss DHP-A Service Instructions Manual

Domestic heat pumps
Table of Contents

Advertisement

Service instructions
°C
ohm, Ω outdoor and defrost sensors
-15
868
-10
681
-5
538
0
428
5
343
10
276
15
224
20
183
25
150
30
124
35
103
40
86
45
50
55
60
65
70
75
80
85
2.3

Check points

Temperatures
Condensing temperature
Evaporation temperature
Superheating
Radiator circuit
Brine circuit
Overheating R407C
Expansion valve factory setting
Danfoss TUBE R404A, 4.2 kW
Danfoss TUBE R404A, 5.6 kW
Danfoss TUBE R404A, 8,4 kW
Danfoss TUBE R404A, 12.0 kW
Danfoss TUBE R404A, 15.3 kW
Danfoss TUBE R407C, 11.0 kW
Danfoss TUBE R407C, 17,0 kW
Refrigerant
R404A (Only applies to the DHP-A models)
8
Domestic heat pumps
1000 ohm, Ω
1000
1039
1078
1117
1155
1194
1232
1271
Values
0,5 – 1,5°C above supply line temperature
7 - 8°C lower than incoming brine
4 - 8 K temperature difference
5 - 10 K temperature difference
2 - 5 K temperature difference
4K ±1 K
Setting
From fully closed position, screw 3 turns out
From fully closed position, screw 5,5 turns out
From fully closed position, screw 5 turns out
From fully closed position, screw 5.25 turns out
From fully closed position, screw 2.75 turns out
From fully closed position, screw 6.25 turns out
From fully closed position, screw 5,5 turns out
Pressure switch
Low pressure switch
Operating pressure switch A
Operating pressure switch B
High pressure switch
VIGFI102
kilo ohm, kΩ other sensors
66,3
52,4
41,8
33,5
27,1
22,0
18,0
14,8
12,2
10,1
8,5
7,1
6,0
5,0
4,2
3,7
3,1
2,7
Break pressure
0.08 MPa
2.65 MPa
2.85 MPa
3,10 MPa
Danfoss Heating Solutions