Cause
3. Defective 3-way valve motor.
The motor should set the valve to the
relevant end position depending on
operating conditions. If it does not, hot
water from the water heater will mix
with the radiator water.
4. Jammed 3-way valve insert.
If the insert is not sealed, hot water
from the water heater will mix with the
radiator water.
Table 32.
Problem – Irregular indoor temperature
Cause
1. The heat pump's control computer
is not set/adjusted to the customer's
requirements/wishes.
2. Incorrectly positioned/installed sen-
sors.
Troubleshooting
Check the function of the 3-way valve
motor by test running it manually. If the
motor does not shift mode during manual
test operation, check that there is voltage
to the motor, see wiring diagram.
Detach the motor and test closing and
opening of the valve by pressing the con-
trol arm.
Troubleshooting
Check the ROOM and CURVE, MIN, MAX
CURVE5, CURVE0, CURVE-5 and HEAT
STOP settings.
Check that outdoor sensors and any room
sensors are installed according to the
instructions and that they are calibrated.
Remedy
Is the motor being supplied with voltage
according to the wiring diagram in both
operating instances?
MANUAL TEST – REV.V. HOT WATER
0=Radiator mode, arm out from the
valve.
1=Hot water mode, arm positioned
towards the valve.
If there is voltage to the motor but the
arm does not shift mode, replace it.
Take out and clean the jammed insert,
or replace with a new insert.
Remedy
Adjust incorrect values in the heat
pump's control computer.
ROOM = Desired indoor temperature
CURVE = Should be set so that the
desired indoor temperature (ROOM) is
maintained regardless of the outdoor
temperature.
MIN = Lowest set-point value on the sup-
ply line regardless of the outdoor tem-
perature (on the condition that heat stop
does not apply).
MAX = Highest set-point value on the
supply line regardless of the outdoor
temperature.
CURVE5,0,-5 =
The supply temperature can be adjusted
up or down 5°C at these outdoor tem-
peratures.
HEAT STOP = Stops all production of
heat when the outdoor temperature is
the same as or greater than the set value.
To exit heat stop the outdoor tempera-
ture must drop to 3°C below the set
value.
Check that the room sensor is posi-
tioned in a suitable place that is rep-
resentative of the building and cali-
brate it if necessary. Avoid placing
near external doors, windows and
heat sources.
Install the outdoor sensor according
to the instructions and calibrate it, if
necessary.
Service instructions VMGFC302 – 53