Write Set Values - Omron E5AN Communications Manual

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

SECTION 4 SYSWAY (E5@J and E5@X Format) Communications Procedures

■ Write Set Values

4-6
• Alarms 1 and 2: Cleared
Note 1. Heater burnout is the status corresponding to heater burnout 1
(CT1).
(3) End Code
When the end code is "00," this indicates normal completion of the
command. Otherwise, the command could not be processed. For
details on end codes, see Response Frame on page 4-3.
(4) Precautions
• Even though alarms 1 and 2 are not displayed on the Controller
display, they function normally in communications.
This command writes the set point, alarm values 1 and 2, proportional
band, integral time, derivative time, temperature input shift values, and
heater burnout detection.
Command
Communi-
Header
Data
cations
code
unit num-
code
ber
@
Response
Communi-
Header
FCS
End
cations
code
unit num-
code
ber
@
(1) Header Code
Header code
WS
W%
WB
WN
WV
WI
WW
(2) Data Code
Set the data code to "02" only when writing alarm value 2. In all other
cases, set to "01."
(3) Write Value
For details on the write value (set value) range, see SECTION 3
Communications Data for CompoWay/F and SYSWAY.
FCS
Termi-
Write
nator
value
CR
*
Termi-
nator
CR
*
Command
Write set point
Write alarm values 1 and 2
Write proportional band
Write integral time
Write derivative time
Write temperature input shift values
Write heater burnout detection

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5gnE5enE5cn

Table of Contents