Omron E5AN Communications Manual page 106

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

SECTION 6 Communications Data for Modbus
Address
Four-
Two-
Parameter name
byte
byte
mode
mode
0600
2600
Manual MV
0602
2601
Set Point
0608
2604
Heater Current 1 Value
Monitor
060A
2605
MV Monitor (Heating)
060C
2606
MV Monitor (Cooling)
0700
2700
Cooling Coefficient
0708
2704
Dead Band
070A
2705
Manual Reset Value
070C
2706
Hysteresis (Heating)
070E
2707
Hysteresis (Cooling)
0710
2708
Control Period (Heating)
0712
2709
Control Period (Cooling)
0718
270C
SP Ramp Time Unit
071A
270D
SP Ramp Set Value
071E
270F
MV at Stop
0722
2711
MV at PV Error
0726
2713
MV Change Rate Limit
072C
2716
Lower Limit Temperature
Input Shift Value
0730
2718
Upper Limit Temperature
Input Shift Value
0734
271A
Heater Current 1 Value
Monitor
0736
271B
Heater Burnout Detec-
tion 1
0738
271C
Leakage Current 1 Moni-
tor
6-4
Setting (monitor) value
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling:
H'FFFFFBE6 to H'0000041A
(−105.0 to 105.0)
SP lower limit to SP upper limit
H'00000000 to H'00000226 (0.0 to 55.0)
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling:
H'00000000 to H'0000041A
(0.0 to 105.0)
H'00000000 to H'0000041A (0.0 to 105.0)
H'00000001 to H'0000270F (0.01 to 99.99)
H'FFFFF831 to H'0000270F
(−199.9 to 999.9 for TC/Pt universal input models)
(−19.99 to 99.99 for Analog input models)
H'00000000 to H'000003E8 (0.0 to 100.0)
H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 99.99 for Analog input models)
H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 99.99 for Analog input models)
H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): 0.5
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): EU/second
H'00000001 (1): EU/minute
H'00000002 (2): EU/hour
H'00000000 (0): OFF
H'00000001 to H'0000270F (1 to 9999)
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling:
H'FFFFFBE6 to H'0000041A (−105.0 to
105.0)
Standard: H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling:
H'FFFFFBE6to H'0000041A (−105.0 to
105.0)
H'00000000 to H'000003E8 (0.0 to 100.0)
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
H'00000000 to H'00000226 (0.0 to 55.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'00000226 (0.0 to 55.0)
Level
Manual
control
Operation
Adjustment
Initial set-
ting
Advanced
function
setting
Adjustment
Operation
Adjustment
Operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5gnE5enE5cn

Table of Contents